eControls Comfort365 C365T11 Manual do instalador e do utilizador - Página 8

Procurar online ou descarregar pdf Manual do instalador e do utilizador para Amortecedores de fogo e fumo eControls Comfort365 C365T11. eControls Comfort365 C365T11 13 páginas.
Também para eControls Comfort365 C365T11: Manual do utilizador (4 páginas), Manual do instalador e do utilizador (13 páginas), Manual do utilizador (4 páginas), Manual do instalador e do utilizador (13 páginas), Manual do instalador e do utilizador (13 páginas), Instalação (2 páginas)

eControls Comfort365 C365T11 Manual do instalador e do utilizador

ACCESSING THE TEST MENU

The Test Menu is used to test the Indoor Fan Operation, Allowable
Heating Airflow Limits and Allowable Cooling Airflow Limits.
The Test Menu can also be used to perform the HERS Total Airflow
test. Option 05-06 activates a cooling call and opens both dampers to
100% enabling the installer to perform the test.
To access the Test Menu,
TOUCH
seconds until the fan test screen (Option 01) appears.
Sleeping
Airflow %
Living
Day
Tu
AM
MENU
MODE
TOUCH
and
to access the Installer Options.
01-02 Testing Indoor Fan Operation
This test is used to verify that the indoor fan is operating correctly.
In Option 1, the Fan is Off.
Touch
NEXT
to go to Option 2
to turn on the indoor fan. Verify
the fan is operating and
delivering airflow to the
sleeping and living area.
Touch
NEXT
to go Testing
Heating Airflow Limits.
03-04 Testing Heating Airflow Limits
This test is used to determine the maximum allowable airflow to the
sleeping area and the living area in HEATING.
In Option 3, the system is Off.
Touch
NEXT
to go to Option 4
to activate heating. Verify the
equipment is operating.
To determine the maximum
allowable airflow to the
Sleeping Area, touch the
UP
key until the airflow is too great
and causes noise or
annoyance. Lower the airflow
using the
DOWN
key until it is
acceptable. This is the
maximum allowable airflow in
heating to the sleeping area.
Record the airflow value.
Maximum Allowable Airflow in Heating to the Sleeping Area
and
HOLD
the hidden Next key for 7
Cool
Set To
Schedule
Living
COOL
SYSTEM
AUTO
FAN
HOLD
this key for 7 seconds
Sleeping
Test
Airflow %
Living
NEXT
ENTER
Sleeping
Test
Airflow %
Living
NEXT
ENTER
Sleeping
Heat
Test
Airflow %
Living
NEXT
ENTER
Sleeping
Heat
Test
Airflow %
Living
NEXT
ENTER
03-04 Testing Heating Airflow Limits (cont.)
To determine the maximum
allowable airflow to the living
area, touch the
DOWN
until the airflow is too great and
causes noise or annoyance.
Increase the airflow using the
UP
key until it is acceptable.
This is the maximum allowable
airflow in heating to the living
area. Record the airflow value.
Maximum Allowable Airflow in Heating to the Living Area
Touch
NEXT
to go to Testing Cooling Airflow Limits.
05-06 Testing Cooling Airflow Limits
This test is used to determine the maximum allowable airflow to the
Sleeping Area and the Living Area in COOLING.
The test can also be used to perform the HERS Total Airflow test. The
test activates a cooling call and opens both dampers to 100%.
In Option 5, the system is Off.
Touch
NEXT
to go to Option 6
to activate cooling. Verify the
equipment is operating.
To determine the maximum
allowable airflow to the
sleeping area, touch the
key until the airflow is too great
FAN
and causes noise or
annoyance. Lower the airflow
using the
DOWN
key until it is
acceptable. This is the
maximum allowable airflow in
cooling to the sleeping area.
Record the airflow value.
FAN
Maximum Allowable Airflow in Cooling to the Sleeping Area
To determine the maximum
allowable airflow to the Living
Area , touch the
DOWN
until the airflow is too great and
causes noise or annoyance.
Increase the airflow using the
UP
key until it is acceptable.
This is the maximum allowable
airflow in cooling to the Living
Area. Record the airflow value.
Maximum Allowable Airflow in cooling to the Living Area
Touch
ENTER
to end testing and return to normal thermostat
operation.
Enter the maximum airflow limits using Options 17
through 20 of the installer menu.
8
Sleeping
Test
key
Airflow %
Living
NEXT
Sleeping
Test
Airflow %
Living
UP
NEXT
Sleeping
Test
Airflow %
Living
NEXT
Sleeping
Test
key
Airflow %
Living
NEXT
Heat
ENTER
Cool
ENTER
Cool
ENTER
Cool
ENTER