3.CONTROLLER INTRODUCTION
2.5) Malfunction Display
During standby or running state ,
if malfunction happens to the
system, the system will stop to
show the malfunction code as
the following:
To show the malfunction code
(refer to malfunction code table)
Ordinary malfunctions and Solutions:
Controller on
Failure
the water tank
Stand by
Unit running
Lower tank water
temp. sensor failure
Upper tank water
temp. sensor failure
Inlet evaporator. temp.
sensor failure
Outlet evaporator
temp. sensor failure
Ambient
temp.
sensor failure
High pressure protect
Low pressure protect
AUX-heating thermal
protect
Communication failure
Defrosting
Indicator
light
Off
On
P01
1
on off
1
2 on 1 off
P02
P03
3 on 1 off
4 on 1 off
P04
5 on 1 off
P05
6 on 1 off
E01
E02
7 on 1 off
E03
8 on 1 off
On
E08
Defrosting
flash
indicate
Bottom sensor failure
Cause
The temp. sensor is open
or short circuit
The temp. sensor is open
or short circuit
The temp. sensor is open
or short circuit
The temp. sensor is open
or short circuit
The temp. sensor is open
or short circuit
1,too much refrigerant in the unit
2,bad heat exchanger on the air
1,the refrigerant is not enough
2,block on the filter or capillary
3,water flow is not enough
4,expansion sensor is broken
The electronic heating temp.
protect
Communication failure
between wire controller
and main board;
12
ALARM
P01
Fig.16
Solutions
Check and replace the temp. sensor for
the upper tank water
Check and replace the temp. sensor for
the lower tank water
Check and replace the temp. sensor for
the evaporator inlet
Check and replace the temp. sensor for
the evaporator outlet
Check and replace the temp. sensor for
the Ambient
1. discharge the redundant gas
2. clean the air side heat exchanger
1.check if there is any leak and refill the gas
2.replace the filter or capillary
3.clean the water side exchanger or discharge
the air in the water loop
4.use new expansion valve
Check the water supply or tank whether
have enough water
Check the wire connection between
the wire controller and the main board