aldes VS6 MAX Manual de instruções - Página 4
Procurar online ou descarregar pdf Manual de instruções para Ventilador aldes VS6 MAX. aldes VS6 MAX 6 páginas. Vs series in-line ventilators
MOUNTING INSTRUCTIONS
(Differences
in
bracket
configuration may exist on some derived
models.
Refer to supplement where
appropriate). Orient the fan so that the
access door can be opened for service.
Tools Required:
Power screwdriver with No. 2 Phillips bit.
Mounting brackets are supplied with
the fan. The brackets may be mounted
to the fan using the self-drilling screws
and rubber grommets provided, at the
locations indicated by dimple marks on
the side and bottom panels of the fan.
Pan head number 10 screws are provided
to attach the mounting bracket to the
building framing members. It may be
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A.
Installation work and electrical wiring must be done
by qualified person(s) in accordance with all applicable
codes and standards, including fire-rated construction.
B.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel-
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guidelines and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
C.
When cutting or drilling into wall or ceiling, do not
damage electrical wiring and other hidden utilities.
D.
When used as exhaust fans, ducted fans must always be
vented to the outdoors.
E.
If this unit is to be installed over a tub or shower, it must
be marked as appropriate for the application and be
connected to a GFCI- (Ground Fault Circuit Interrupter)
protected branch circuit.
F.
NEVER place a switch where it can be reached from a tub
or shower.
MOUNTED VERTICALLY
necessary to add additional framing
type
and
members to span wall studs. It is not
recommended to use drywall anchors
to support the fan. If installed against
a concrete or masonry wall, concrete
anchors are recommended. The rubber
grommets provide vibration isolation.
The brackets should be attached to the
fan first. Then install the wood screws at
the keyhole locations and install the fan.
The fan may also be mounted on a foam
rubber pad on a flat surface, such as an
attic floor.
COLD CLIMATE PRECAUTIONS
If installed in an unheated space in
cold climates, there is a possibility of
condensation forming in the fan housing
FANS MAY BE
OR HORIZONTALLY
ELECTRICAL DATA
Provide disconnect switch in vicinity of fan to permit servicing fan in
accordance with NEC and local codes.
Depending on the desired mode of operation, switches may be
simple on-off switches, motor speed controls, timer switches, time
delay, time-of-day cycle timers, dehumidistats, occupancy sensing
controls, controllers, etc., provided they are rated for the motor duty
and meet the nameplate electrical ratings of the motor. (Additional
application wiring diagrams illustrating a variety of controls for use
with RDF fans are available by calling the factory at 1-800-255-7749.)
Base Model
RDF 8-8IP
RDF 8-8MAX
RDF 12-8IP
RDF 12-8
RDF 8-8MAX and RDF 12-8
RDF SUPPLEMENT
or ducting components.
damper installed at each grille is an
effective way to reduce the potential for
condensation when the fan is cycled on
and off. Insulated ducting must be used
where exposed to cold attic or crawl space
temperatures to avoid condensation in
the ducting. Condensation can also be
avoided by continuous operation of the
fan.
DUCT CONNECTIONS
Ducting may be flexible or rigid,
depending on local codes. If permitted
by code, insulated flexible ducting is
recommended. To limit fan noise, at least
8 feet of insulated flexible duct shall be
installed between the fan and grille(s). All
flexible duct connections shall be secured
with clamps or wire ties and sealed with
mastic or code-approved duct tape. All
rigid ducts are to be sealed on both ends
and along the longitudinal seams with
mastic or code-approved duct tape.
Ducting should conform to NFPA 90A and
meet the requirements of UL as a Class 0
or Class 1 duct to specification UL 181,
Standard for Factory-Made Air Ducts and
Duct Connectors.
Max
Max
Volts
Amps
Watts
115
0.19
21
115
0.29
34
115
0.34
41
115
0.53
59
RDF 8-8IP and RDF 12-8IP
2
A backdraft
RPM
2500
3135
2200
2960