Clark Cooper EH40-08 Manual de instalação e operação - Página 3

Procurar online ou descarregar pdf Manual de instalação e operação para Unidade de controlo Clark Cooper EH40-08. Clark Cooper EH40-08 7 páginas.

Built in filters are now being offered.
Sealing:
Six different valve seat leakage classifications are defined by ANSI/FCI 91-2-2004. All valves
must pass a leakage test prior to the leaving the factory based on the requirements of this
specification.
This standard leakage for the EH40 product is Class 2. Class 5 is available.
Electrical:
Electrical wiring must conform to the nameplate rating. Wiring, conduit, and conduit
connections must comply with National and Local Electrical Codes. The standard solenoid
enclosure has a ½" NPT conduit connection. Standard lead wires supplied are 18" long, and are
wire gauge size 18 AWG minimum. The wire used to connect to the power source should be the
same or heavier gauge. Cables extending from ATEX approved coils are 3000mm [118"].
Custom leads lengths may be available upon request.
941 Hamilton avenue
Roebling, nj 08554
www.ClarkCooper.com
Page 3 of 7