Clary Corporation DT1000RET Manual do Proprietário - Página 13

Procurar online ou descarregar pdf Manual do Proprietário para UPS Clary Corporation DT1000RET. Clary Corporation DT1000RET 16 páginas. Dtr (et) series continuous power system

SPECIFICATIONS

ELECTRICAL
Input
Voltage
Power Factor Corrected
Frequency
Current
Output
Voltage
Frequency
Current
Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical
Total Harmonic Distortion (THD)
Dynamic Response
Overload
Efficiency (UPS)
UPS Protection
ENVIRONMENTAL
Operating Temperature
Humidity
Altitude
Audible Noise
MECHANICAL
Input
Output (Qty.)
Cooling
Dimensions: In. (mm)
Weight: Lbs. (Kg)
HxWxD
T H E C O N T I N U O U S P O W E R C O M P A N Y
120VAC +12%, -25%
(without Battery discharge)
IAW MIL STD. 1399 Sec. 300
45 to 65Hz
7.2 A
120VAC ± 3%
50Hz / 60Hz (software select)
Line Sync (software select)
8.3 A
@50% Load
Up to 4.8:1
@75% Load
Up to 3.2:1
@100% Load
Up to 2.4:1
3% Typ; 5% Max.
(@100% Non-linear load)
±4% for 100% Step Load Change,
0.5 Millisecond Recovery Time
110% for 10 Minutes;
200% for 0.5 Seconds
85-87% Typical
Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge
o
o
o
o
-40
C(-40
F) to +74
C(+165
F)
0% to 95% Non-condensing
Sea Level to 10,000 Feet
46 dBA at Five Feet
NEMA 5-15P Plug w/6' Cord
(4) NEMA Type 5-15R Outlets
Low Velocity, Forced Air
3.5 (89)x19.0 (483)x18.0 (457)
30 (13.5)
DESIGN
Standard Features
Specifications
MTBF
Typical Recharge Time to
85% Capacity at 100% Load
CONTROLS AND INDICATORS
Visual Indicators
Sequenced LEDs
Single LED
Front Panel Controls
Audible Alarms
RS232 Data Interface (DB-
9F)
Open-Collector (DB-9F)
Optional SNMP Interface
(RJ45 or BNC)
Specifications subject to change without notice.
Page 13
Power Factor Corrected, Digital
Regenerative™ On-Line, Sinewave
Inverter Powers Load Continuously
Extended Brownout Protection
Designed for Non-linear Loads
Continuous Operation on
-25%,+12% Line
Automatic Bypass
RS232 Data Interface
Software Selectable Output
Frequency
AC Output Switch
Auxiliary Battery Connector
Rear Mounted Ground Stud
Optional SNMP Interface
UL 1778, CUL, FCC Class A,
IEEE 587/ANSI C62.41,
IEC 555 @ 120VAC
In Excess of 100,000 Hours
8 Hours
Battery Level, Load Level
AC Input, Inverter On, Load On
Summary Alarm, Alarm Silence,
Cold Start,
Power On, Cold Start
Alarm Silence, Battery Test
AC Output On/Off
Utility Interrupt, Inverter Failure
Overload, Low Battery
Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.
Compatible with Systems
TM
Enhancement
UPS Monitor &
Control Software
Allows Alarm Function Monitoring
Allows Full Control and Monitoring
Over Network Connection.
2/2001