1MRS 752265-MUM
0RWRU 3URWHFWLRQ 5HOD\
Installation Manual
6HPLIOXVK PRXQWLQJ
The semi-flush mounting kit (1MRS050696) includes a raising frame, a gasket and
screws and is needed for the semi-flush mounting of a case. The gasket is used when
an IP 54 degree of protection (according to the IEC 60529) is required for the front
side. If the gasket is not used, an IP 50 degree of protection is obtained.
Mount the raising frame to the cut-out in the panel with four screws according to
.
4.4.-1
Caution!
!
A device equipped with optic connections requires a minimum
depth of 130 mm
Panel
Raising frame
)LJ
6HPLIOXVK PRXQWLQJ
M4 screws
173.5
+0.3
-0.3
Ø 5.5
+1
165.5
-1
Dimensions of panel cut out
Case
5(0
Fig.
11