Armstrong DSA-92 Manual de instalação e operação - Página 11

Procurar online ou descarregar pdf Manual de instalação e operação para Humedecer Armstrong DSA-92. Armstrong DSA-92 18 páginas. Humidifiers for air handling systems

Multiple Manifolds – See Page 7 for required pipe sizes and dimensions of manifolds with pipe adapter.
Piping Multiple Manifolds – Figure 9-3 below shows the standard installation of reduced size manifold. Note the steam
Figure 9-1. Pipe Connection at Humidifier
Figure 9-3. Piping of Reduced Size Manifolds
Figure 9-4. Piping of Same Size Manifold When All Manifolds Are Above Humidifier Inlet
jacketing is trapped separately and the steam discharge is into a tee, not a cross. A cross will
cause uneven steam distribution from manifold to manifold.

Multiple Manifolds

Figure 9-2. Manifold Pipe Adaptor
Chart 9-1. Header Size of Manifold Piping Out of Humidifier
Separator
Minimum
Size
Pipe Size
90
91
92/1200
93/1300
94/1400
Humidifier discharge piping, even with reduced sized
manifolds must be as shown.
When same size manifolds (as the
separator) are used, the piping can
eliminate the drain trap from the
manifold jacket. Note that steam now
discharges into an elbow, not a cross,
and that the manifold steam jackets
are not trapped separately.
Note: The humidifier steam inlet is
below the bottom manifold. If the
bottom manifold is below the
humidifier inlet, piping should be as in
Figure 9-3.
Note: When steam supply pressure is
less than 10 psig and total length of
manifolds is greater than 20 feet, trap
manifolds separately as shown in
Figure 9-3.
Suggested
Header Size
/
"
/
"
1
3
2
4
/
"
2"
1
2
3
/
"
2
1
/
"
4
2
1"
3"
2"
5"
9