Armstrong FLO-RITE-TEMP 415 Instruções de instalação e ajuste - Página 2

Procurar online ou descarregar pdf Instruções de instalação e ajuste para Aquecedor de água Armstrong FLO-RITE-TEMP 415. Armstrong FLO-RITE-TEMP 415 17 páginas. Inverted bucket steam traps
Também para Armstrong FLO-RITE-TEMP 415: Instruções de instalação e ajuste (20 páginas), Descrição do produto (4 páginas)

Armstrong FLO-RITE-TEMP 415 Instruções de instalação e ajuste

INSTALLATION AND ADJUSTMENT INSTRUCTIONS

No water heater will work satisfactorily if improperly installed and operated. These instructions contain
important information for the installation and adjustment of the FLO-RITE-TEMP Water Heaters. Read
these instructions carefully before installing this unit. FAILURE TO ADHERE TO THESE
INSTRUCTIONS COULD RESULT IN SERIOUS BODILY INJURY OR PROPERTY DAMAGE.

STEAM PIPING INSTALLATION OF A SINGLE UNIT

Single and Double Wall

NOTE: FLO-RITE TEMP is provided with (1) one Armstrong Steam Trap and Thermostatic
Air Vent (shaded). All other items shown not included.
NOTE: units may be piped in parallel for larger capacity requirements. See Fig. 15-1 for an example of
parallel unit installation.
The unit includes the mixing valve mounted to the heat exchanger, channel iron and U-bolts mounted,
thermostatic air vent installed on the heat exchanger, a water pressure pop off valve integral to the unit control
valve and a separate Armstrong Inverted Bucket Steam Trap.
1.
Install the FLO-RITE-TEMP with adequate room to allow for tube bundle removal when cleaning is
required. See Table 12-1 for specific dimensions.
2.
If 2-15 psig of steam is available a pressure reducing valve is NOT required. If a pressure reducing valve is
required, an Armstrong Inverted Bucket Steam Trap is recommended to drain condensate at the inlet of the
pressure reducing valve.
October 31, 2002 @ 3:15 pm
FLO-RITE-TEMP

INSTANTANEOUS WATER HEATER

NOTICE
Steam
In
Armstrong Pressure
Reducing Valve (If Req'd)
GP-2000
Armstrong
I.B. Trap
Armstrong Thermostatic
Air Vent
2-15 psig Steam
in the Shell
Vacuum Breaker
Armstrong
I.B. Trap
STEAM SIDE INSTALLATION
(Refer to Fig. 2-1)
Safety Relief
Valve
Gate
Valve
Pressure
Gauge
Fig. 2-1
2