Acorn Safety S0002 Instruções de instalação, operação e manutenção - Página 4

Procurar online ou descarregar pdf Instruções de instalação, operação e manutenção para Equipamento para relva e jardim Acorn Safety S0002. Acorn Safety S0002 5 páginas. Drench hoses

Installation & Operation Manual
OPERATION INSTRUCTIONS:
Employees who work with hazardous materials should
become familiar with the location and operation of the
nearest emergency plumbing fixture. Emergency
plumbing fixtures stations are simple to use and require
hands free operation once the station is activated.
Regular instruction regarding proper care and use will
increase confidence that the units are accessible and
function properly.
The route and area surrounding the Eye Wash should
be clear and unobstructed; the sooner eyes are flushed,
the less likelihood of damage. Eye Wash stations should
be located in close proximity to the hazard and take no
more than 10 seconds to reach. In the case of sever eye
contamination the victim may require assistance to the
Eye Wash station and help flushing their eyes.
Safety plumbing fixture equipment should be operated
weekly for a period long enough to verify operation,
clear the supply line of any sediment build-up and
minimize microbial contamination due to sitting water.
1. To start the Drench Hose, squeeze handle. Flushing
should start, popping the spray nozzle caps open.
2. Lower eyes into flow. Both eyes should be flushed to
prevent contamination from one eye from being
delivered to unaffected eye. Personnel who wear
contact lenses should remove them immediately prior
to or during the flush to prevent the contamination
from remaining against the cornea possibly causing
unnecessary damage or pain.
3. Using thumb and forefingers, fully open eyelids and
flush eyes thoroughly for approximately 15 minutes or
until medical personnel arrive. Be prepared to let the
doctor know what type of contamination has entered
the eye.
4. When finished release the handle and return drench
hose assembly to standby position. Flushing fluid
should stop. Once flushing fluid has stopped flowing,
return spray nozzle lids to the closed position to
protect from airborne contaminates.
MAINTENANCE GUIDE:
Maintain and inspect in accordance with ANSI Z358.1-
2009
1. Check for obvious signs of wear, broken or defective
equipment. Re-paint if necessary. Replace missing or
defective equipment such as broken push paddles,
missing signs and inspection tags.
2. Remove strainer and washout any debris collected
–replace as required.
3. Operate Drench Hose by squeezing handle, checking
for smooth operation of valve push paddle
mechanism at the same time ensuring that the drench
hose spray nozzle caps pop off immediately when
actuated. If the ball valve does not operate smoothly
check the actuating assembly for binding or missing
parts. If the
Acorn Safety
a division of Acorn Engineering
Manual #7109-500-001
Drench hose spray nozzle caps do not pop off
immediately when actuated check for correct supply
inlet pressure.
4. While in operation, inspect spray nozzles for clogs or
debris correct or replace as required.
5. Release the handle. To prevent drench hose spray
nozzles from becoming contaminated, always close
nozzle lids after each use.
Company
Page 4 of 5
Revised: 03/22/13