8.6 Firmware Update

• Right-click on the reader and select Firmware update
menu (8.18)
• On the Firmware update window, click on the Browse
button (8.19). The default location of the firmware files
installed with CAMS is in the folder "Firmware".
• Select the firmware file with a "xhc" extension.
• Click on the Upload button
Important: Wait for the update end message. Do not turn
off the reader, the software or any communication device
in between during the entire process.

8.7 Sensor Calibration

• Right click on the biometric reader and select
"Calibrate" and wait for confirmation message.
Note: It is recommended to do a calibration while
commissioning the reader and in cases when there
are problems with reading the fingers

8.8 Send Configuration

• Right-click on the reader and select the Send
configuration menu
• See the events panel to check the configuration flow
Note: The biometric reader gets its settings
automatically. This function is used if the reader was
off line while making the changes.
Page 11 of 19
CV-940 Series
8.18
8.19
8.20