Art. No. 11231
New, switch one Shutter Pro output with defined runtime
To switch the relay output with a defined runtime of the Shutter Pro use the following command for the 1-Wire
Controller or ESERA Station, which only sets the selected function 1 = Down and 2 = Up with a defined runtime
with a final stop.
Note: The function is supported from controller firmware 1.20_27. If you want to use this function, a
firmware update of the 1-Wire Controller may be necessary.
Command: SET,OWD,SHT,OWD- Number, Value, Time
The following times can be selected:
Runtime for Up and Down function
250 milliseconds (ms)
500 milliseconds (ms)
750 Milliseconds (ms)
1 bis 60 seconds
The Shutter Pro makes a stop after the run time. This switches off the outputs and stops the shutter.
After switching the output, the new state is output as confirmation via the 1-Wire interface. The output value 0
corresponds to the rest position of the Shutter Pro.
There is no feedback at the elapsed time or at the runtime.
Data output 1-Wire controller / ESERA Station 200
For the Shutter Pro switching module the following data are output for the status of the relay output.
Data output:
1_EVT|12:27:40
1_OWD1_1|1
1_OWD1_2|00000001
1_OWD1_3|7
1_OWD1_4|00000111
Further information for options and commands can be found in the latest available documentation for
1–Wire Controller / 1–Wire Gateway.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Input for command
250
500
750
1 -60
=> Controller No._Module No._Data set | decimal value input
=> Controller No._Module No._Data set | binary representation input
=> Controller No._Module No.-_Data set | decimal value Shutter status
=> Controller No._Module No._Data set | binary representation Shutter status
11231 V2.0 R1.0 Manual
Example
set,owd,sht,2,1,250
=> OWD Number 2 is switched to
„DOWN" for 250ms.
set,owd,sht,2,1,500
=> OWD Number 2 is switched to
„DOWN" for 500ms.
set,owd,sht,2,1,250
=> OWD Number 2 is switched to
„DOWN" for 750ms.
set,owd,sht,2,1,34
=> OWD Number 2 is set to
„DOWN" for 34 seconds.
Page 5 of 7