Maintenance
Procedures
(continued)
Figure 3 – Sleeve Bearing
TABLE 3. Sleeve Bearing Lubricants
TEMP AMBIENT
B.A.C. P/N
70°F to 110°F
#582628PI
30°F to 70°F
5°F to 30°F
#582627PI
-25°F to 5°F
CAUTION: Do not use oils containing detergents for
bearing lubrication. Detergent oils will remove the
graphite in the bearing sleeve and cause bearing fail-
ure. Also, do not disturb bearing alignment by tight-
ening bearing cap adjustment on a new unit as they
are torque adjusted at the factory.

FAN MOTOR BEARINGS

All Totally Enclosed Fan Cooled (TEFC) Fan Motors have
regreaseable bearings. The motor bearings should be
lubricated as recommended in the motor manufacturer's
operating instructions that are attached to the motor when
the equipment ships from the factory.

LOCKING COLLARS

Each eccentric locking collar should be checked
every six months to ensure that the inner bearing
race is secured to the fan shaft. The locking collar can
be set using the following procedure (see Figure 4):
1. Loosen the set screw.
2. Using a drift pin or centerpunch, tap the collar (in the
hole provided) tangentially in the direction of rotation
while holding the shaft.
3. Retighten the set screw.
10
OIL CUP
TEXACO
EXXON
Regal R & O 320
Teresstic 220
Regal R & O 150
Teresstic 100
Regal R & O 32
Teresstic
32
Capella
32
DIRECTION
OF ROTATION
Figure 4 – Locking Collar Assembly

ADJUSTABLE MOTOR BASE:

The motor base slides and adjusting screw (See Figure 5)
should be coated twice a year using a good quality corro-
sion inhibiting grease such as one of those recommended
for lubricating the fan shaft bearings (see Page 9).
Figure 5 – Adjustable Motor Base
VTO, VT1, VTL, VF1, VFL, VC1, VCL
ADJUSTABLE MOTOR BASE:
The motor base hangers, hinges, and adjusting screw
(See Figure 5A and 5B) should be coated twice a year
using a good quality corrosion inhibiting grease such as
one of those recommended for lubricating the fan shaft
bearings (see Page 9).
MOTOR
BASE
HANGERS
Figure 5A – Adjustable Motor Base
VC2-N138-N446
DRIFT
PIN
(A) TAP THE LOCKING COLLAR
IN DIRECTION OF FAN ROTATION
(B) TIGHTEN SET SCREW
AFTER CAM IS LOCKED
ADJUSTING
NUT
LOCK NUT
ADJUSTING SCREW
ADJUSTING