esera automation 11220 Manual do utilizador - Página 4
Procurar online ou descarregar pdf Manual do utilizador para Interruptor esera automation 11220. esera automation 11220 7 páginas. 8-fold switch module with pushbutton inputs for 1-wire bus
8
Operating mode, display and operation
The module has two modes of operation: normal mode and manual control mode.
Normal mode: After start-up, the device is in normal operation mode. This means that a command is applied
directly by the 1-Wire interface to the appropriate output relay. The respective output LED is lit.
Manual control mode: By pressing the button „MAN/Select" for 2 seconds, the module switches to manual
control mode (manual operation). The „PWR" LED flashes to confirm selection of manual control mode.
Press the "MAN / Select" key briefly to select an output. The LEDs 1-8 light up for the selected output. Press the
"ON / OFF" key to switch the selected output on or off.
Several outputs can be switched in one cycle.
After a waiting time of approx. 2 seconds, the system automatically switches to the operating mode "normal
operation", the "PWR" LED lights up again permanently and the selected outputs are activated.
Delete "Manual operation": Pressing the "ON/OFF" key for 2 seconds switches off the outputs selected in
manual operation.
Display
Designation
LED 1-8
Output 1-8
LED PWR
Power
LED Status
Status display
manual control
mode
Button
Designation
MAN/Select
Operating mode /
Channel selection
ON/OFF
Output 2 On/Off
9
8-fold digital input, pushbutton Interface
In addition to the manual mode (module top side), and the 1-Wire interface, the module also has
8-fold pushbutton interface, 8 x digital / binary input, for switching the outputs.
To switch an output, a short input signal (keystroke) to the corresponding input is sufficient.
The 8-fold pushbutton interface is intended for switching lights, actuators for radiators or sockets in the living area
by e.g. light switches or motion detectors with pulse output. This ensures fast switching even with no system
control available.
The impulse control, comparable to a staircase lighting timer, allows any number of light sensors and motion
detectors to be connected at the same time.
Further details on the ESERA-Automation lighting system can be found on the following website:
https://www.esera.de/smart-home/anwendungsbeispiele/lichtsteuerung/
Besides light scanners, any other pulse control signal can be used to switch the outputs.
All three interfaces, manual operation, 1-Wire and push button interface, operate in parallel to the outputs. An
output switched e.g. by the 1-Wire interface can be switched off or on manually or by push button interface.
The pushbutton interface can be used for example to connect light scanners for light on/off control. Normal light
scanners of all switch manufacturers can be used for this purpose.
Within the module a µController takes over the query of the buttons, the 1-Wire interface and the control of the
relays. The button interface is queried via edge scanning.
The outputs switched via the pushbutton interface or manual operation can be read back via the 1-Wire interface.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
LED function
- LED is lit for 2 seconds on system start-up
- Normal mode: LED display is lit when the output is active
- Manual control mode: Select the output to be switched on or off
with the „Select" button
- LED flashes 2 seconds to start the system
- LED is lit when an output relay is active
- LED flashes in the manual control mode
- LED is lit for 2 seconds on system start-up
- Status display of the selected output after switch to normal mode
operation (relay on or off)
Button function
The button has two different functions
- Switch to manual control mode (press for 2 seconds)
- Select output (press briefly)
The button has two different functions
- Selected output On / Off (press briefly)
- Delete all outputs of manual control mode (press for 2 seconds)
11220 V2.0 R1.0 Manual
Page 4 of 7