dixell WING XW40LS Instruções de instalação e de utilização - Página 3
Procurar online ou descarregar pdf Instruções de instalação e de utilização para Termostato dixell WING XW40LS. dixell WING XW40LS 3 páginas.
dIXEL
2.
Automatically the parameter list of the "Hot Key" is downloaded into the Wing memory, the
"doL" message is blinking. After 10 seconds the instrument will restart working with the new
parameters.
3.
Turn OFF the instrument remove the "Hot Key", plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
"End " for right programming. The instrument starts regularly with the new programming.
"Err" for failed programming. In this case turn the unit off and then on if you want to restart the
download again or remove the "Hot key" to abort the operation.
8.2 UPLOAD (FROM THE INSTRUMENT TO THE "HOT KEY")
1.
Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if
present; then turn it ON again.
2.
When the Wing unit is ON, insert the "Hot key" and push
appears.
3.
Push "SET" key to start the UPLOAD; the "uPL" message is blinking.
4.
Turn OFF the instrument remove the "Hot Key", plug in the TTL serial cable, then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
"end " for right programming.
"err" for failed programming. In this case push "SET" key if you want to restart the programming again
or remove the not programmed "Hot key".
9. ALARM SIGNALS
Message Cause
"P1"
Thermostat probe failure
"HA"
Maximum temperature alarm
"LA"
Minimum temperature alarm
"EE"
Data or memory failure
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the "P1" which is
flashing. To reset the "EE" alarm and restart the normal functioning press any key, the "rSt" message is
displayed for about 3s.
9.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing any key.
9.2
"EE" ALARM
The dIXEL instruments are provided with an internal check for the data integrity. Alarm "EE" flashes
when a failure in the memory data occurs. In such cases the alarm output is enabled.
9.3 ALARM RECOVERY
Probe alarm: "P1" (probe1 faulty), automatically stops 10s after the probe restarts normal operation.
Check connections before replacing the probe.
Temperature alarms "HA" and "LA" automatically stop as soon as the thermostat temperature returns
to normal values or when the defrost starts.
10. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 40mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws.
Distance between the holes 165mm
Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Faston 2.8mm for probe heat-resistant wiring and 6,3mm Faston for loads and supply
Power supply: 230Vac or. 110Vac
10%
±
Power absorption: 4VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC or PTC probe
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 8(3) A, 250Vac
fan: relay SPST 8(3) A, 250Vac
Other output : alarm buzzer (optional)
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20
85% (no condensing)
÷
Measuring and regulation range: PTC probe: -50÷150°C (-58÷302°F)
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit
11. CONNECTIONS
11.1 XW40LS
L
8(3)A
Fan
N
N
Hot - Key
8(3)A
L
Light
WARNING: Because of direct load connections, main voltage 230V is present in the faston of
loads, when the instrument is powered.
1598002153 XW40LS GB VCS r1.0 06.12.2006.doc
Installing and Operating Instructions
o
key; the "uPL" message
Outputs
Alarm output ON; Compressor output according to
parameters "COn" and "COF"
Alarm output ON; Other outputs unchanged
Alarm output ON; Other outputs unchanged
Alarm output ON; Other outputs unchanged
3 x 2mm.
∅
N
20(8)A
Comp
L
L
Max 20A
N
12. DEFAULT SETTING VALUES
Label Name
REGULATION
Set
Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
OdS
Outputs activation delay at start up
AC
Anti-short cycle delay
CCt
Compressor ON time during fast freezing
COn
Compressor ON time with faulty probe
COF
Compressor OFF time with faulty probe
CH
Type of regulation
DISPLAY
CF
Temperature measurement unit
rES
Resolution (integer/decimal point)
DEFROST
EdF
Defrost mode
IdF
Interval between defrost cycles
MdF
(Maximum) length for 1° defrost
dFd
Displaying during defrost
dAd
MAX display delay after defrost
dPO
First defrost after start up
dAF
Defrost delay after fast freezing
ALARMS
ALC
Temperature alarms configuration
ALU
MAXIMUM temperature alarm
ALL
minimum temperature alarm
AFH
Temperature alarm differential
ALd
Temperature alarm delay
dAO
Delay of temperature alarm at start up
EdA
Alarm delay at the end of defrost
ANALOGUE INPUTS
Ot
Thermostat probe calibration
OTHER
Pbc
Kind of probe
rEL
Software release
Ptb
Map code
Prd
Probes display
Pr2
Access parameter list
Dixell S.p.A. Via dell'Industria, 27
32010 Z.I Pieve d'Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com
XW40LS
rel.1.0 - cod. 1598002153
Range
Default
Level
°C/°F
LS÷US
2
Pr1
0,1÷25,5 °C / 1÷45°F
1
Pr1
-50,0°C÷SET / -58°F÷SET
-10
Pr2
SET ÷ 110°C / SET ÷
10
Pr2
230°F
0÷255 min.
1
Pr2
0÷30 min.
1
Pr1
0 ÷ 23h 50 min.
0
Pr2
0÷255 min.
15
Pr2
0÷255 min.
5
Pr2
CL, Ht
CL
Pr2
°C ÷ °F
°C
Pr2
in ÷ de
dE
Pr1
In, Sd
in
Pr2
1÷120h
7
Pr1
0÷255 min.
60
Pr1
rt, it, SEt, dEF, dEG
it
Pr2
0÷255 min.
30
Pr2
n ÷ y
n
Pr2
0 ÷ 23h 50 min.
0
Pr2
rE÷Ab
rE
Pr2
-50,0÷110°C/ -58÷230°F
8
Pr1
-50,0÷110°C/ -58÷230°F
2
Pr1
0,1÷25,5 °C / 1÷45°F
1
Pr2
0÷255 min.
15
Pr2
0 ÷ 23h 50 min.
1.3
Pr2
0÷255 min.
20
Pr2
-12,0÷12,0°C / -21÷21°F
0
Pr1
PbC, ntc
ntc
Pr2
- - -
2.0
Pr2
- - -
-
Pr2
Pb1
Pr2
- - -
Pr1
3/3