3HS RMS-V II Manual de instalação - Página 12

Procurar online ou descarregar pdf Manual de instalação para Alarme de fumo 3HS RMS-V II. 3HS RMS-V II 13 páginas. Ceiling mounted visual smoke detector

Installationshandbuch RMS-D II und RMS-V II

Technical Data

Model
Voltage supply
Periodic and random
deviation
Power Input
Switch contact:
for Error
-
for Alarm
-
- Contact voltage
- Switching current
- Switching power
Function display
Operation
-
Error
-
Alarm
-
Surrounding
temperature
Storage temperature
Rel. Humidity
Protection system
According
to
DIN
400500
Weight
Installationshandbuch: RMS-D II und RMS-V II Relais
®3HStrading GmbH&Co.KG, Königsheimer Strasse 13,
D-78603 Renquishausen, Tel. 07429 33 61 Fax. 07429 91 61 335,
12 Volt
+ 12V DC, +/- 10%
< 20%
~ 44 mA
Floating output
Changeover contact
Changeover contact
100V DC / 125V DC
1,0 A
30W / 62,5 VA
Green blinking
Yellow
illuminating
red/yellow alternating
Red illuminating
0° C to max. 50°C
Max. 80 ° C
Max. 90 %
IP 40
~ 100 g (RMS-D II)
~ 500 g (RMS-V II)
Model
Voltage supply
Periodic and random
deviation
Power input
Switch contact:
for Error
-
for Alarm
-
- Contact voltage
- Switching current
- Switching power
Function display
Operation
-
Error
-
Alarm
-
Surrounding
Temperature
Storage Temperature
Rel. Humidity
Protection system
According
to
DIN
400500
Weight
www.3HS.de
24 Volt
+ 24V DC, +/- 10%
< 20%
~ 22 mA
Floating output
Changeover contact
Changeover contact
100V DC / 125V DC
1,0 A
30W / 62,5 VA
Green blinking
Yellow illuminating
red/yellow alternating
Red illumination
0° C to max. 50°C
Max. 80 ° C
Max. 90 %
IP40
~ 100 g (RMS-D II)
~ 500 g (RMS-V II)
Seite 12 von 13
Stand: 01.12.2015
Version:2.7