8.0 INITIAL CONFIGURATION
8.1 The CDM-2100 is pre-configured for measuring the differential catalyst pressure
using the Altronic differential pressure transmitter. All of the basic labels and
configuration are already complete for the user to start monitoring. However,
there are site specific parameters that should be updated. This section will guide
the user through the minimum screens required to set-up the controller. A more
detailed description of all user parameters is provided in section 10.
This system is shipped with factory default settings. Upon power-up a splash
screen displays: DSG-1611DUPS, the firmware Rev. Level, and date.
Once the arrow cursor is adjacent to the line to be changed, pressing the ENTER
key changes the icon to
é
change the selection. Once the desired change is made, pressing the ENTER key
saves the change and returns the arrow cursor.
Press the MENU key to enter into the main system menu.
The up and down arrow keys can be used to move the cursor down to the
PREVIOUS MENU. Pressing ENTER then returns the display to the main menu.
Move the cursor adjacent to SETPOINTS and press ENTER.
UNITS
FILTER
~SETPOINTS
CONFIGURE
CALIBRATE
RESET
COMMUNICATIONS
SECURITY
UNITS
FILTER
~SETPOINTS
CONFIGURE
CALIBRATE
RESET
PREVIOUS MENU
An LED is tied to the output of Switch 2, such that when a fault occurs the LED
will illuminate. According to the manufacturer of the catalyst there will be an end
of life pressure. Switch output 2 should be set such that the LED indicator will
alert someone visually before the end of life pressure of the catalyst. Optionally
Switch 1 is wired to terminals, and can be configured to operate an external relay
or digital input to notify a control system of the elevated catalyst pressure.
CHANNEL 1
~ HI
LO
HYST
PREVIOUS MENU
CDM-2100 OM 3-21
All rights reserved © ALTRONIC, LLC 2021
. Now the up and down arrow keys can be used to
inH2O
254
CHANNEL 1
psi
254
6in H2O
0in H2O
3 SEC
NOTE: The splash screen can be
displayed at anytime from a home
screen by pressing both the up and
down arrow keys together.
ENTER
ENTER
5