from the menu, use or to scroll to RESET and press ENTER. The display
will show RESET!. A reset can also be performed by sending a reset command
via the RS-485 Modbus RTU communications register.
8.5.1
MIN/MAX READING
Use the or arrow key to point to MIN/MAX READING and press ENTER;
The display will show RESET!. RESET resets both the min and max readings to
the current reading.
RESET:
~MIN/MAX READING
PREVIOUS MENU
8.6
COMMUNICATIONS
8.6.1
The CDM-2100 gauge is part of a system that has been carefully designed to
easily interface to popular computers, terminals, programmable controllers
and Altronic instruments. Modbus RTU is the protocol used in the CDM-
2100. A Modbus register list with register numbers and descriptions of
each register can be found in section 10.0. The serial communications are
compliant to the Modicon Modbus RTU standard and uses RS-485 for its
hardware communication format. To view or adjust the communication
parameters, select COMMUNICATIONS from the main menu and press
ENTER. Throughout the menu use the or arrow keys to make a selection
and press ENTER to save the changes.
FOR DETAILED COMMUNICATIONS INFORMATION SEE SECTION 9.0.
COMMUNICATIONS
~NODE:
BAUD:
PREVIOUS MENU
8.6.2
NODE
The node number gives each gauge on the communications port an identity.
Any node number from 1 to 99 can be used. Use the up and down arrow keys
to select a node number and press ENTER to save.
8.6.3
BAUD — Select the required baud rate and press ENTER to save.
SEE SECTION 9.3 FOR AVAILABLE BAUD RATES.
8.7
SECURITY
8.7.1
The security feature allows for a user to lock the gauge to secure chosen areas
of the menu from being changed. There are several individual areas in the menu
system that can be protected as well as two layers of protection. The menus
that can be protected are the CONFIGURATION menu settings, the SETPOINT
values, the ability to make changes via modbus COMMUNICATIONS, and
CDM-2100 OM 3-21
All rights reserved © ALTRONIC, LLC 2021
CHANNEL 1
1
9600
8