Dimensions
Electrical connection
After opening the front cover, the electrical connection is made by using screw terminals.
Readjustment of the zero point
The zero point can be, regardless of the menu, readjust with a small bar magnet.
Adjustment:
The device is not within the menu.
Remove the pressure connections from the device.
Touch with the bar magnet the side of the zero point adjustment.
The new zero point will be stored.
Terminals:
1+ 2-
Excitation 10...30 Vdc
or 24 Vac (+/-15%)
3+ 4-
Output 0...10 V
5 6
floating contact input for
setpoint 1 or 2
side of adjustment
N
S
zero point