Arthur Grillo DS200 Manual de instalação e operação - Página 11

Procurar online ou descarregar pdf Manual de instalação e operação para Acessórios Arthur Grillo DS200. Arthur Grillo DS200 16 páginas. Differential pressure sensor

Arthur Grillo DS200 Manual de instalação e operação
5.3 Adjustable parameters - hardware
Damping levels: In case of fluctuating measured values different damping levels can be
adjusted via the DIP-switches no.1 and no. 2.
No damping
Time constant
Time constant
Time constant
Choice of analogue input:
The analogue output can be switched via a jumper from voltage 0/2...10V
down) to 0/4...20 mA
current output or a burden adjustment.
0,5 s
1s
1,5 s
DIP-switch
(horizontal up). The potentiometer P1 allows fine tuning of the
Doc.-no.: DS200_01_EN
DIP 1
DIP 2
off
off
on
off
off
on
on
on
jumper
Issue: 05/2017
OPERATION
(horizontal
11