1 - BEFORE STARTUP
Your Cleaver-Brooks boiler has been factory fire-tested and the control system pre-configured for a trouble-
free startup. To help ensure a successful lightoff and reliable operation, certain initial conditions should be
observed.
Do not attempt to place the boiler into service without verifying that all connections - fuel, steam and
water piping, electrical connections, stack, and combustion air provisions - have been installed properly
and in accordance with any applicable codes or regulations.
CHEMICAL FEED

1.1 Operating Conditions

• The installation site should be as free as possible from vibration, dust, and corrosive media
• The controllers should be located as far as possible from sources of electromagnetic fields, such as
frequency converters or high-voltage ignition transformers
• Control panel must be connected to earth ground. For electrical wiring requirements, see wiring diagram
provided with the boiler or in the CFH manual.
Boiler room ambient conditions
Relative humidity
Ambient temperature range
Storage temperature range
Combustion air temperature
Specifications
Input power
Recommended operating steam
pressure
Gas pressure requirements
Part No. 750-293
SURFACE
BLOWOFF
GAS SUPPLY
Figure 1 CFH Connections
< 85% non-condensing
o
o
0
C to 50
C / 32
o
o
-20
C to 60
o
o
0
C to 50
C / 32
115 VAC single phase 60Hz
Up to 135 psig (150# design)
Up to 13.5 psig (15# design)
See Table 1
COMB. AIR/
DIRECT VENT
GAUGE GLASS
DRAIN
o
o
F to 122
F
o
o
C / -4
F to 140
F
o
o
F to 122
F
CFH Startup Guide
STEAM OUTLET
CHEMICAL FEED
FEED WATER
WATER COLUMN DRAIN
BLOWDOWN
Warning
!
W h e n u s i n g d i r e c t v e n t
combustion in cold climates,
special care must be taken to
o b s e r v e
c o m b u s t i o n
temperature limits. Failure to
follow this precaution may lead
to equipment damage or unsafe
operation.
STACK OUTLET
a i r
3