Cleerline SSF-TKITP-500 Manual de início rápido

Procurar online ou descarregar pdf Manual de início rápido para Equipamento de teste Cleerline SSF-TKITP-500. Cleerline SSF-TKITP-500 2 páginas.

Cleerline™ SSF-TKITP-500
WARNING: LIGHT SOURCE LASER DOES NOT OPERATE AT VISIBLE WAVELENGTH. LIGHT IS NOT VISIBLE WHEN LASER
IS ACTIVE. TO AVOID THE RISK OF EYE DAMAGE, DO NOT LOOK AT LASER WHEN LIGHT SOURCE IS OPERATIONAL.
Your power meter and light source units will be used to measure loss in dB of the power coupled into the cable by the light source
versus power measured on the receiver end by the power meter. Loss testing is done at wavelengths for the fiber in use, typically
850 nm for Multimode and optionally at 1300 nm, while Single Mode is tested at 1310 nm and optionally 1550 nm. The measured
loss can be compared to the estimated loss for the link or "loss budget."
This testing kit with included OLS, OPM, reference cables, adapters, power supplies, and available software allows for loss testing
and data recording of fiber optic cables
For set-up, allowable loss, link budget calculations, etc., the Fiber Optic Association (FOA) is a great resource for testing guidelines.
FOA power testing instructions are included with your kit and should be reviewed prior to using this equipment. Information on the
two noted tests above can be found via the FOA at www.thefoa.org, including fiber optic testing methods and standards.
1. Turn on both light source (OLS) and power
meter (OPM).
Set both the OPM & OLS to the desired wave-
length by pressing the wavelength button on
each unit.
2. On the OLS press FREQ button until CW displays
on the center of the screen below the wavelength
(see step 1A image).
*Typical testing configuration for most cables
CLEERLINE™
TEchnology group
Test Kit Quick Start Guide
A. Wavelength on the OLS is displayed in the
upper right corner of the screen. Set to desired
value (press wavelength key.)
Pressing wavelength button activates laser.
3. On both units ensure that the auto-power off
funtion is not ON before setting any reference.
If set to ON quick press the power button 1x to
turn off the auto feature.
Note: a power symbol will be at the top of the
screen if the auto-off function is on.
B. The OPM should be set to same wavelength
as the OLS unit. Press the wavelength button
until desired value appears.
Note: Typically 850nm for Multimode testing
and 1310nm for Single Mode. *Use appropriate
cables for fiber type being tested.*
Aqua = Multimode. Yellow = Single Mode.
TOP VIEW
4. Plug REFERENCE cable into the appropriately
labeled port on the OLS.
LC Single-ended testing - 1 cable between OLS &
OPM *install LC adapter onto OPM.
LC Double-ended testing - 2 cable between OLS &
OPM *install SC adapter onto OPM.
SC Single-ended testing - 1 cable between OLS &
OPM *install LC adapter onto OPM.
cleerline.com
1
2
3
4
5
6
7
Date: 5/25/2023 Rev 1.1
8