c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked
[+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm
condition). Jumper J3 must be cut (Fig. 3, pg. 6).
6. FACP Dry form "C" output (Fig. 1a, pg. 5):
Connect desired device to be triggered by the unit's dry contact output to the terminals marked [NO] and [C]
FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
7. Installation of tamper switch (Not Included):
Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2" from the right side.
Connect tamper switch wiring to the Listed Access Control Panel input or the appropriate UL Listed
reporting device to activate alarm signal when the door of the enclosure is open.
Unit should be tested at least once a year for the proper operation. Voltage on each output has to be tested
for both trigger and non-trigger states and operation of FACP interface has to be simulated.
LED
LED 1 - LED 4 (Red)
TRG (Green)
Terminal Legend
- - Power +
- - Control +
TRIGGER
INPUT 1 - INPUT 4
IN, GND
OUTPUT 1 - OUTPUT 4
NC, C, NO, COM
FACP INTERFACE
T, + INPUT - -
FACP INTERFACE
NC, C, NO
- 4 -
Maintenance:
LED Diagnostics:
ON
Output relay(s) energized.
FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Terminal Identification Table:
Function/Description
12VDC to 24VDC input from UL Listed Access Control Power Supply.
These terminals can be connected to a separate, UL Listed Access Control
Power Supply to provide isolated operating power for the ACM4/ACM4CB
(jumpers J1and J2 must be removed).
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir's, etc.).
12 to 24 volts AC/DC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO become form "C" 5A 24VAC/VDC rated dry outputs when
fuses are removed (ACM4). Contacts shown in a non-triggered state.
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally
open, normally closed from an FACP output circuit (Fig. 3 through 7, pg. 6-7).
Form "C" relay contact rated @ 1A/28VDC for alarm reporting.
(This output has not been evaluated by UL).
OFF
Output relay(s) de-energized.
ACM4 Series