AKO 55724 Manual do utilizador - Página 10

Procurar online ou descarregar pdf Manual do utilizador para Sistema de segurança AKO 55724. AKO 55724 16 páginas. Gas leak detection alarm

6.- Configuration

Alarm Station
AKO-55624
No configuration needed
AKO-55724
The
input auto-detection
It is only necessary to follow these steps:
Step 1
When receiving a power supply for the first time, the alarm enters
INPUT AUTO-DETECTION MODE, lighting up the input indicators
sequentially in green.
Step 2
Select the 2 or 4 area operation mode using the Mute push-button.
Step 3
Begin AUTO-DETECTION by pushing the 'AUTOCONFIG' push-button
for 5 seconds (See page 4). At the end of the process, the alarm will
emit 5 short beeps and will begin to function normally.
For correct input detection, all devices must be correctly
connected and in NO ALARM mode, including the push-
buttons connected in digital inputs.
Once the alarm has been configured, this function will not be activated again. To activate it again,
disconnect the power supply, connect it again and press the "AUTOCONFIG" pushbutton 5 times
consecutively within 2 minutes and repeat step 2 within another 2 minutes.
All Models
Self-diagnosis function
The device incorporates a self-diagnosis system which informs the user in the event of a transmitter / detector
malfunction or if there are wiring errors.
If a malfunction is detected, the alarm will emit 3 short beeps every 2 minutes and the corresponding input
indicator will flash red.
Pre-alarm jumper
It allows deactivating pre-alarm detection (See page 4). Before using
this option, make sure that regulations allow for only one alarm
level.
Pre-alarm enabled
When using the ammoniac or CO2 transmitter / detector, the pre-alarm must be enabled.
function facilitates station configuration.
Pre-alarm disabled
10
1
ON
OFF
2
3
5572H402 Ed.03