ETA-20SH SPECIFICATIONS
General
Type
Power Requirements
Power Consumption
RoHS Compliant
Panel
Switched Outlets
Spike & Surge Suppression
Manual Override
Extreme Voltage Shutdown
Connectors
Fuse Protection
DCV Remote Trigger
Remote Trigger
Status Signals
Indicators
Power Cord
Technical Data
Current Rating
Operating Voltage
High Voltage Surge Protection
Spike & Surge Suppression
Low Voltage Protection
Spike Protection Modes
Minimum Spike Clamping Voltage
Maximum Spike Clamping Voltage
Maximum Spike Clamping Response Time
Spike Clamping Voltage @ 100A
Maximum surge current
Energy Rating @ 2ms
Noise Attenuation EMI/RFI Sequencer
Temperature Range
Humidity Range
Mechanical
Chassis Finish
Mounting
Dimensions
Weight
Agency Listings
ETA-20SH
AC Power Conditioning & Suppression Module
AC Power Conditioner & Suppressor Module
120V 60Hz
.5W
Yes
Two, 20A
H-N, N-G, H-G
Slide switch
(EVS) Below 101V or Above 132V AC Line (When Used With ETA-ECS6RM)
5 Position Phoenix Euro Block Style
20A Slow Blow
5 – 24DCV
SPST Contact
Output for Voltage and Current Data (All Signals are Low Voltage and Low Current)
Incoming AC, Active, AC Fault
9 ' (3M), 12-gauge NEMA 5-20P 125v AC plug
20 amps
102 to 132 VAC
Trigger at 133VAC, 1ms Typically (When Used With ETA-ECS6RM)
H-N, N-G, H-G
Trigger 101 VAC, 1ms Typically (When Used With ETA-ECS6RM)
Circuitry on Incoming AC Mains.
460 VRMS @ 3,000 amps
6000v
1 nanosecond
1250Vp for 20µs
6,500 amps
600 Joules
10dB @ 10kHz, 40dB @ 100kHz, 100dB @ 10MHz
5° to 35°
C
5% to 95% R.H.
Black
Side bracket adjustable
3.0" H x 8.5" D x 3.5" W (76mm x 216mm x 89mm)
5.5lbs (2.49kg)
MET (UL1449 Code)
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
– 15 –
Specifications are subject to change without notice.
ETAsys.com