Technical Data
Wire connection
Cross section:
Stripping length:
Wire fixing:
Fixing torque:
Mounting:
Weight:
Dimensions
Width x height x depth:
Classification to DIN EN 50155
Vibration and
shock resistance:
Ambient temperature:
Protective coating of the PCB: No
UL-Data
Meas. ciruit L1(+)/L2(-) to PE1/PE2 (with coupling device RL / RP 5898)
Max. voltage range U
:
N
Output voltage at
L(+)/L(-), VSG1/VSG2:
Temperature range
Operation:

Switching capacity:

Wire connection:
Test specification:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
CCC-Data
Switching capacity
To AC 15
NO contact:
NC contact:
Technical data that is not stated in the CCC-Data, can be found
in the technical data section.
nfo
DIN 46228-1/-2/-3/-4
0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
6.5 mm
Cross-head screw / M3 box terminals
0.5 Nm
DIN rail
IEC/EN 60715
Approx. 205 g
52.2 x 90 x 71 mm
Category 1, Class B
IEC/EN 61373
OT1, OT2 compliant
RL 5898
RP 5898
AC 0 ... 400 V
AC 0 ... 600 V
DC 0 ... 500 V
DC 0 ... 600 V
Max. AC / DC 230 V
- 30 ... + 60 °C
Pilot duty C300, R300
5A 250Vac
2A 30Vdc
60 °C / 75 °C copper conductors only
Torque 0.5 Nm
ANSI/UL 60947-1, 5
Edition
th
ANSI/UL 60947-5-1, 3
Edition
rd
CAN/CSA-C22.2 No. 60947-1-13,
2
Edition
nd
CAN/CSA-C22.2 No. 60947-5-1-14,
1
Edition
st
3 A / AC 230 V
1 A / AC 230 V
Standard Types
RN 5897.12/240/61
Article number:
• Auxiliary voltage:
RN 5897.12/240/61
Article number:
• Auxiliary voltage:
RN 5897.12/240/61
Article number:
• Auxiliary voltage:
• Outputs:
• Setting range alarm:
• With connection facility of a coupling device RL 5898 or RP 5898
• Max. line capacitance:
• Energized or de-energized on trip
• Selection of type of network
• Width:
Ordering Example for variants
RN 5897 .12 /020 /61 AC/DC 24 ... 60 V 1 kΩ - 100 kΩ 20 kΩ - 500 MΩ
6
DC 12 ... 24 V
0069124
DC 12 ... 24 V
AC/DC 24 ... 60 V
0069123
AC/DC 24 ... 60 V
AC/DC 85 ... 230 V
0069125
AC/DC 85 ... 230 V
1 changeover contact for device fault
1 changeover contact for alarm
1 kΩ ... 500 kΩ
5 µF
52.5 mm
Setting range Pre-warning
Setting range alarm
Auxiliary voltage
UL approval
Variant, if required
Contacts
Type
17.03.21 en / 371A