Blueridge BM12M22CNS Manual de instalação - Página 14

Procurar online ou descarregar pdf Manual de instalação para Manipuladores de ar Blueridge BM12M22CNS. Blueridge BM12M22CNS 20 páginas. Low-wall air handler

Blueridge BM12M22CNS Manual de instalação

Refrigerant Piping Connection

Note on Pipe Length

The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 16.5ft. In North America, standard pipe length is 25'.
A minimum pipe run of 10 feet is required to minimize vibration & excessive noise. Refer to the table
below for specifications on the maximum length and drop height of piping
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
12k
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure
efficient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.
 Page 14 
Max Length
Max Drop Height
82 feet
Add'l Refrigerant
33 feet
6
0.16/ foot
Revised 5/14/2020