Refrigerant Piping Connection
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 16.5ft. In North America, standard pipe length is 25'.
A minimum pipe run of 10 feet is required to minimize vibration & excessive noise. Refer to the table
below for specifications on the maximum length and drop height of piping
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
18k
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure
efficient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.
Revised 5/14/2020
Max Length
Max Drop Height
98 feet
Add'l Refrigerant
33 feet
6
0.16/ foot
Page 11