Appendix B

LPPK Setup for Blue Ridge Technologies Digi-Touch Switches

Purpose:
Assign DDN-SW1 or DDN-SW2 switches to LPPK Groups in order to control the correct lighting circuits and report the Group status
back to the correct DDN-SW1 or DDN-SW2 button LEDs.
Steps:
1) Start LPPK. Go to main page as shown below. In the section, "Input # - Name", note the fixed input numbers along the left side fo
the page.
2) Go to the section "Assigned group", and to the column, "0-60". Assign a Group # to the input box. For each input, assign a Group
number. The Group number must equal the switch address. In other words, the Group # = the Input # = DDN dip switch # as shown
in the diagram. Note the fixed Input # on the left side of the page is in line with the Group # in the white input box on the right side of
the page.
3) Remember, the DDN dip switch # represents the upper button. Dip switch # + 1 represents the lower button. Include both numbers
in LPPK.
4) Set the Input Type to Momentary On/Off and Normally Open. Standard switches to the same panel are not required to follow this
"Input# = Group#" configuration.
Example: DDN-SW2 switches will command panel Groups 1-4. DDN-SW2 switches will also have an optional 2-hour timer and flash
enabled. The status of the panel groups are reported back to the correct DDN-SW2 LED. Standard switches control all other groups.
Dip Switch Numbers
are entered into LPPK
as Input Numbers and
Group Numbers.
Standard Input
Assignments
w w w. b r t i n t. c o m
Blue Ridge Technologies is a Trademark of Blue Ridge Technologies
© 2010 Blue Ridge Technologies International, LLC All Rights Reserved.
Dip Switch Setting (under cover plate) is
assigned to each DDN-SW upper button.
Note
Add 1 for the lower button.
Multiple DDN switches can have the same dip switch setting.
Switches with the same see will control the same groups.
Note
Digi-Touch
Installation Guide
Dip Switch Number
is the Group Number
that will be used for
the status LEDs.