Ambirad SmartCom 3 Руководство - Страница 3

Просмотреть онлайн или скачать pdf Руководство для Контроллер температуры Ambirad SmartCom 3. Ambirad SmartCom 3 18 страниц.

NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for all remote sensors.
GND
L2
L1 (HOT)
Exhaust
Fan
(n.c.)
SmartCom Mulitizone
Burners
(Slave 1)
Zone B
41
40
7
8
R
C
40VA
L2
Trans
L1
G
S-0700
Relay
Burners
SmartCom Mulitizone
Zone A
(Master)
41
40
7
8
R
W1
C
S-0755
Relay
S-0700
G
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0 S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
Black Bulb
Sensor
GND
120V 60Hz 1 Ph
L2
15 amp Supply
L1 (HOT)
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0 S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
Black Bulb
Black Bulb
C
Sensor
Sensor
40VA
L2
120V 60Hz 1 Ph
Trans
20 amp Supply
L1
GND
Relay
L2
L1 (HOT)
To other slave
controllers
eg E.M.S.
Outside
To other slave
Sensor
controllers
(where applicable)
eg
E.M.S.
Drawing No. :
900290 R6 USA