To turn off the latch one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the letter 'L' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the 'oF' option.
5. To confirm the change, press the SET button.
7.6
Signaling of the sensor failure 'CA', 'CU'
For full control of the measurement chain AVM 1002DX can activate alarm/warning outputs when the
measurement chain or vibration sensor is damaged.
Sensor failure alarm can be attributed to the triggering alarm or warning relay. Triggering of the relay
occurs after 5 seconds of open/short sensor failure.
To set up the sensor failure signaling on the alarm output one should perform the following
procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'CA' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the ON option.
5. To confirm the change, press the SET button.
To set up the sensor failure signaling on the warning output one should perform the following
procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into
2. the device menu.
3. By pressing UP/DN set the 'CU' on the display.
4. Confirm by pressing the SET button.
5. Use the UP/DN buttons to select the ON option.
6. To confirm the change, press the SET button.
To turn off the sensor failure signaling 'CA'/'CU' one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'CA'/'CU' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the 'oF' option.
5. To confirm the change, press the SET button.