Novus manual 0916-1 24/11/2016 13:43 Page 5

Location of the unit

Clearances to non-combustible
materials
• Novus
There is a recommended minimum
clearance of 150mm at each side of the
appliance. A clearance of 150mm is
required at the back of stove (if the rear
wall has a thickness of 200mm or more
this measurement can be reduced to
50mm) a minimum clearance of 300mm
is required above the appliance.
Clearances to combustible
materials
• Novus
There must be a minimum clearance of
300mm at each side of the appliance and
there must be a minimum clearance of
200mm at the rear of the appliance from
any combustible materials. If using single
wall flue pipe, there must be a clearance
of at least 3 times the diameter of the flue
pipe (e.g. 150mm diameter pipe =
450mm minimum clearance) from any
combustible materials e.g. wooden
beam.
Curtains and soft furnishings should be a
minimum of 1m away from the appliance.
Adequate space should be provided for
servicing the appliance.
We do not recommend that televisions or
artwork are positioned above the
appliance.
Please remember that this appliance has
been designed to provide heat and if
installed into a recess enough space
should be left around the appliance to
enable the heat produced to rise and
escape from the recess back into the
room.

Installation Instructions

Hearth Requirements
The appliance must stand on a level
fireproof hearth with a minimum thickness
of 12mm. The hearth temperature
created by this stove is below 100˚C. The
hearth must protrude at least 225mm in
front of the appliance and 150mm either
side of the appliance.
The appliance shall be installed on a floor
with an adequate load bearing capacity. If
an existing construction doesn't meet
with prerequisite, suitable measures
(e.g.load distributing plate) shall be taken
to achieve it.
Flue Requirements
The chimney must comply with current
Building Regulations. Provision must be
made to provide access for cleaning the
appliance, the flue gas connector and the
chimney flue.
The flue must be:
In sound condition and provide sufficient
draft (minimum 12 Pa)
Suitable for use with solid fuel burning
appliances
Be able to clean the entire length of the
flue system without removal of the
appliance
Free from deposits
Well insulated
At least 4m in height
The flue must not be:
Shared with other appliances
Weight bearing on the appliance
A smaller diameter than the appliance
flue collar size (150mm)