nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.(not possible
to put them on after flaring work)
Flaring
Firmly hold copper pipe in a die in the
dimension shown in the table below.
(Inch)
Max.
Min.
1/J'
1/U
1/U
3/~
,
1/U
1/U
1/~
,
1/~J
1/J1
Copper tube
Copper pipe
• Align the center of the pipes ..
• Sufficiently tighten the flare
--------=..o!--~JJ~-f)~-- ~I
rD----,lrT"""
Indoor unit tubing
Flare nut
nut with fingers, and then tighten
it with a spanner and torque wrench
as shown.
Fig.18
Outer
are n
Fig.16
Red arrow mark
.17
Fig.19
Tightening Additional VJ.htening
diam.
torque(N.cm)
torque( .cm)
1570
1960
• Excessive torque can break nut
depending on installation conditions.
1/4 '
(160kgf.cm)
(200kgf.cm)
3/J'
2940
3430
(300kgf.cm)
(350kgf.cm)
1;~
J
4900
5390
(500kgf.cm)
(550kgf.cm)
Electric safety regulations for the initial Installation
1. If there is serious safety problem about the power supply, the technicians should refuse
to install the air conditioner and explain to the client until the problem is solved.
2. Power voltage should be in the range of 900/0"'"'11
o
0/0 of rated voltage.
3. The sorge protector and main power switch with a 1.5 times capacity of Max. Current
of the unit should be installed in power circuit.
4. Ensure the air conditioner is grounded well.
5. According to the attached Electrical Connection Diagram located on the panel of the outdoor
unit to connect the wire.
6. All wiring must comply with local and national electrical codes and be installed
by qualified and skilled electricians.
7. An individual branch circuit and single receptacle used only for this air conditioner must be
available. See the following table for suggested wire sizes and fuse specifications: