3.9 Ducting Arrangements - Standard Unit Configuration
3.9.1 Circular Ducting
10
Exhaust air from
kitchen/bathroom to
outside via louvre grille.
Minimum distance as specified
in building regulations.
Intake air
from outside
via louvre grille.
All duct between MVHR
unit and atmosphere to
be insulated*.
3.9.2 Rectangular Ducting
11
Exhaust air from
kitchen/bathroom to
outside via air brick.
Minimum distance as specified
in building regulations.
Intake air
from outside
via air brick.
All duct between MVHR
unit and atmosphere to
be insulated*.
671950 | DeCembeR 2020
*Insulated
extract duct.
Top of ceiling void.
*Insulated
supply duct.
Nuaire wall
mounted unit.
Typical Circular Ducting Arrangement For Wall mounted Units
*Insulated
extract duct.
Top of ceiling void.
*Insulated
supply duct.
Nuaire wall
mounted unit.
Typical Circular Ducting Arrangement For Wall mounted Units
Air supply
to lounge
via Air Valve
in ceilings.
MVHR-DRAIN
Condensate drain, uninsulated
o
drain pipe with min 5
fall running to SVP.
Air supply
to lounge
via Air Valve
in ceilings.
MVHR-DRAIN
Condensate drain, uninsulated
o
drain pipe with min 5
fall running to SVP.
Air supply to
bedrooms
via Air Valve
Extract air
in ceilings.
from
kitchen/
bathroom
via Air Valve
in ceilings.
Air supply
to bedrooms
via Air Valve
Extract
in ceilings.
air from
kitchen/
bathroom
via Air Valve
in ceilings.
PAGe 6