SINGLE STAGE FURNACE / SINGLE STAGE COOLING
COMFORT CONTROL
SINGLE STAGE
TERMINAL BLOCK
GAS FURNACE
24VAC HOT
R
R
SINGLE STAGE
G
G
FAN
AIR CONDITIONER
Y
Y
COOLING
HEATING
W
W
Required
B
C
TWO STAGE GAS FURNACE - SINGLE STAGE COOLING
COMFORT CONTROL
TWO STAGE
TERMINAL BLOCK
GAS FURNACE
24VAC HOT
R
R
SINGLE STAGE
G
G
FAN
AIR CONDITIONER
Y
Y
COOLING
W
HEATING
W1
W2
Required
B
C
SINGLE STAGE AIR HANDLER W/ELECTRIC HEAT - SINGLE STAGE COOLING
COMFORT CONTROL
SINGLE STAGE
TERMINAL BLOCK
AIR HANDLER
24VAC HOT
R
R
G
G
FAN
Y
Y
COOLING
W
W
HEATING
360 ohm
5 watt
B
C
Resistor Required
SINGLE STAGE AIR HANDLER W/ELECTRIC HEAT
(NO OUTDOOR UNIT)
SINGLE STAGE
COMFORT CONTROL
TERMINAL BLOCK
AIR HANDLER
R
R
24VAC HOT
G
G
FAN
Y
Y
COOLING
W
W
HEATING
B
C
Required
Pub. No. 11-HD03D1-3
Figure 3
Resistor is required on Y to B
Y
at the indoor unit low voltage
terminal block when outdoor
unit contactor coil is not directly
connected to Y or if a compressor
anti-short cycle timer has been
B
installed.
Figure 4
Resistor is required on Y to B
Y
at the indoor unit low voltage
terminal block when outdoor
unit contactor coil is not directly
connected to Y or if a compressor
anti-short cycle timer has been
B
installed.
Figure 5
SINGLE STAGE
AIR CONDITIONER
Resistor is required on Y to B
Y
at the indoor unit low voltage
terminal block when outdoor
unit contactor coil is not directly
connected to Y or if a compressor
anti-short cycle timer has been
B
installed.
Figure 6
Resistor is required on Y to B
when outdoor unit contactor
coil is not connected to Y.
360 ohm
5 watt
Resistors
Installer's Guide
SINGLE STAGE OIL FURNACE / SINGLE STAGE COOLING
SINGLE STAGE
COMFORT CONTROL
OIL FURNACE
TERMINAL BLOCK
R
R
24VAC HOT
G
G
FAN
Y
Y
COOLING
W
W
HEATING
R1
B
C
OIL BURNER PRIMARY
T
R1
T
SINGLE STAGE OIL FURNACE (NO OUTDOOR UNIT)
COMFORT CONTROL
SINGLE STAGE
TERMINAL BLOCK
OIL FURNACE
R
R
24VAC HOT
G
G
FAN
Y
Y
COOLING
W
W
HEATING
R1
B
C
OIL BURNER PRIMARY
T
R1
T
Figure 7
SINGLE STAGE
AIR CONDITIONER
Resistor is required on
Y
Y to B at the indoor unit
low voltage terminal block
when outdoor unit contactor
coil is not directly connected
to Y or if a compressor anti-
short cycle timer has been
B
installed.
Figure 8
Resistor is required on Y to B
when outdoor unit contactor
coil is not connected to Y.
360 ohm
5 watt
Resistors