Valve Servicing Dimensions
A
FLOW
The following tables detail the recommended minimum valve servicing dimensions.
Globe
Size (in)
1 1/4
1 1/2
A (in)
16
16
B (in)
10
10
Angle
Size (in)
1 1/4
1 1/2
C (in)
16
16
D (in)
10
10
Setting the Float Control Valve
Opening and Closing Speed – Turn the adjustment screws on the Closing Speed and Opening Speed Controls, if the main valve is so
equipped, OUT, counterclockwise, 1½ to 2½ turns from full closed position.
STEP 1
To ensure proper operation, any trapped air will need to be bled
off the valve cover during startup. The ACV includes a bleed
valve, use a flat head screwdriver to slowly open the valve (See
Figure 1).
STEP 2
Pressure the line, by opening the upstream isolation valve slowly.
Air is vented through the air bleed valve. Tighten the fitting when
liquid begins to vent (See Figure 1).
IOM-A-ACV-972-19_672-19 2115
B
FLOW
2
21/2
3
4
20
22
22
24
12
14
14
16
2
2 1/2
3
4
20
22
22
24
12
14
14
16
FLOW
6
8
10
32
34
38
24
26
28
6
8
10
32
34
38
24
26
28
Counterclockwise to OPEN
bleed valve
EDP# 1917110
C
FLOW
12
14
16
20
44
48
52
30
34
40
12
14
16
44
48
52
30
34
40
Figure 1
Position Indicator
© 2021 Watts
D
24
56
56
48
48
3