Commissioning
Maximum Temperature
The maximum blend temperature obtainable by the user should be limited to
prevent accidental selection of a temperature that is too hot.
The T301 tap is fully performance tested and the maximum temperature is preset
to 41°C under ideal installation conditions at the factory. Site conditions and
personal preference may dictate that the maximum temperature has to be reset
following installation.
Maximum Temperature Setting
Make sure that an adequate supply of hot water is available at the hot inlet of the
T301.
The minimum temperature of the hot water must be at least 10°C above the
desired blend. However, during resetting this should be close to the typical storage
maximum to offset the possibility of any blend shift due to fluctuating supply
temperatures.
Make sure that both inlet isolating valves are fully open.
Temperatures should always be measured using a thermometer with proven
accuracy.
Guide to maximum stabilised temperatures recorded during site tests (Table 3)
Wash Basin
Commissioning must be carried out in accordance with these
instructions, and must be conducted by designated, qualified
and competent personnel.
Application
Mixed Temperature °C
9
43