Ametek Magnetrol SOLITEL Руководство по установке и эксплуатации - Страница 3

Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Переключатель Ametek Magnetrol SOLITEL. Ametek Magnetrol SOLITEL 13 страниц.

Figure 1
56-601 Solitel Vibrating Rod Level Switch
1.0
Introduction
The Solitel
Vibrating Rod Level Switch provides reliable
®
level detection of bulk solids and powders. This compact,
integral switch is suitable for high or low level detection
in hoppers and silos. It may also be used for plugged
chute detection.
The rugged, single-piece probe is suitable for use in a
variety of powders or granular materials with a minimum
bulk density of less than one pound per cubic foot.
1.1

Principle of Operation

The Solitel
®
rod vibrates at a 350 Hz frequency. When
media makes contact with the rod, the vibration is damp-
ened. The attenuation of the vibration is detected by the
integral mount electronics, changing the status of the relay.
2.0

Installation

2.1
Unpacking
Unpack the instrument carefully. Make sure all compo-
nents have been removed from the packing material.
Inspect all components for damage, and report any
concealed damage to the carrier within 24 hours.
Check the contents of the carton, making sure it agrees
with the packing slip and the purchase order. Verify that
the model number imprinted on the nameplate matches
the number on the packing slip and the purchase order.
Report any discrepancies to the factory. Check and record
the serial number for future reference when ordering parts.
2.2
Mounting
Prior to installation, it is recommended that the unit be
calibrated using a sample of the media to be measured.
Refer to Calibration, Section 2.5.
IMPORTANT: Handle the instrument with great care,
especially the probe. Any impact on the probe can damage
the vibration system.
Serial Number
3