3.3
Programming the Unit
To be adjusted for a specific way to use, the unit provides programming the following parameters
which are stores in its non-volatile memory.
The configuration parameters are described in Table 9.
Parameter
Initial Output
Status
On/Off Events
Circuit Failure
Detection Type
Open-Circuit
Failure Monitoring
Type
Open-Circuit
Failure Current
Current
Calibration Factor
Code of State 1
Code of State 2
Code of State 3
Code of State 4
Code of State 5
Threshold 1-2
Threshold 2-3
Threshold 3-4
Threshold 4-5
Restore Time
10
Description
Parameters of Outputs
The output control program
to be started after powering
up or resetting the unit as
well as on receiving a Switch
the Output to Initial Status
command
Generating events on
changing states of the output
relay
The value defining monitored
conditions of the monitored
circuit
Defines the tactics for the
unit to monitor an activated
output when an open circuit
failure has occurred
The value of the minimum
current in the monitored
circuit for the monitoring
type "Programmable Open-
Circuit Threshold"
The value for estimating the
current at the output. This
value is written to the
memory of the unit at the
factory during manufacturing
and cannot be edited
Parameters of Inputs
Defines indication and
messages transmitted to the
network controller
The resistance values of
inputs which separates the
states
The integral time for restore
conditions
Table 9. Configuration Parameters
Value
ON / OFF
ON / OFF
Any value
Open and Short Failures
from Table 3
Any value
from Table 4
5 mA to
2.5 A
Fire Equipment Failure
Any value
Fire Equipment Restored
from Table 1
Fire Equipment Failure
0...50 kOhm
0...255 s
Default Value
OFF
ON
Normal
5 mA
Loop Short Circuit
Loop Open Circuit
100 Ohm
3 kOhm
7 kOhm
12 kOhm
5 s