FIXING INSTRUCTIONS
Technical Data TS 99 FLR-K
Input:
Output:
Type of Protection:
Protection class:
Smoke switch:
Temperature:
Technical Data, Hold-open Device (EMF)
Operating voltage:
Power input:
Duty factor:
• Work on electrical equipment and systems may
only be performed by properly trained specialist
personnel.
• Check to ensure that the line power supply (230V
AC) has been disconnected and is no longer live.
• IA 10 A/B miniature circuit breaker must be
provided in the supply circuit. This can also be
used as the isolator for disconnecting the FLR-K
and making it dead.
• The power cable leading to the FLR-K must be
properly secured to ensure effective strain relief.
• The power cable (NYM) conductor cross section
should be not greater than max. 1.5 mm
conductor is not electrically utilised. The terminal
(PE) should, however, be used where a PE
conductor is provided.
• Fire/smoke detectors controlling hold-open
systems must not be used to actuate any further
alarm devices (e.g. fire alarm transmission
systems).
• If the optional alarm module is installed, the cable
connecting it to the smoke switch must be led over
and across the measurement chamber in order to
ensure that smoke penetration is in no way
hindered.
• According to the guidelines for hold-open systems
issued by the Institute of Building Technology,
Berlin, it must be possible to release every hold-
open device by manual means. If free-swing door
closers are used, release must be initiated by a
manual pushbutton. The manual release
pushbutton used for this must be red and carry the
inscription "Close Door". The pushbutton must be
in the immediate vicinity of the door (barrier) and
must not be concealed when the door (barrier) is
open.
Integral lintel-mounted smoke detector.
Electro-magnetic hold-open device.
Ceiling-mounted smoke detector.
DORMA HT manual release pushbutton for hold-
open devices.
1 )
1 )
1 )
1 )
1 )
Guidelines for hold-open systems issued by the Institute for Building Technology,
Berlin. In countries outside Germany, consult local regulations.
TS 99 FLR-K EN 2-5
230 V AC +10%/-15%
120 mA/28 VA / 50 Hz
24 V DC /460 mA / 11 W
IP 30
II
24 V DC/50 mA
-20°C/+60°C
24 V DC
2 W
100 % continuous duty
The PE
2
1)
Installation arrangement of the FLR-K for
a
applications where the bottom surface of the ceiling
is less than 1m above the bottom edge of the lintel
on one or both sides of the door.
See separate sheet for associated connection
diagrams.
b
If the bottom surface of the ceiling is more than 1m
above the bottom edge of the lintel on one or both
sides of the door, two ceiling-mounted smoke
detectors must be installed in addition to the lintel-
mounted detector (FLR-K)
See separate sheet for associated connection
diagrams.
1
Drill fixing points for closer and slide channel using
TS 99 FLR-K template or as per dimensioned
2
drawing.
3
Drill holes of 12 mm dia. for the 230V AC power
cable (by others) and of 10 mm for connection to the
TS 99 FL, manual pushbutton and any required
ceiling-mounted detectors. Install cabling.
4
Fix junction box.
5
Fix mounting backplate.
6
Fix closer to the mounting backplate.
Ensure that the cable is located in the mounting
backplate groove and that it remains undamaged.
7
Connect 24V DC supply cable to the junction box
terminal
.
Connect interconnecting cable
Connect the internal cable to the connector of the
electro-hydraulic hold-open device
8
Fit arm at an angle of approx. 10° from the door leaf
and tighten fixing screw
9a
LH (ISO 6) handing:
Fix FLR-K unit.
9b
RH (ISO 5) handing:
Rotate slide channel 180°
Fix FLR-K unit.
10
Close valve for adjusting closing speed
door approx. 45°
.
11
Push arm towards slide channel
slide block
.
12
Adjust spring strength (closing force).
13
Adjust closing speed 180° - 0°
Adjust latching action 7° - 0°
14
Fit end caps
.
Break out spindle recess tab
Ensure that the cables are not damaged in this
process.
Clip on DORMA logo badge
1) 1) 1) 1) 1)
1) 1) 1) 1) 1)
.
.
.
, and open
and connect to
.
.
and fit clip-on cover
.
.