Advance Appliances ECB 210 Руководство по установке и эксплуатации - Страница 7

Просмотреть онлайн или скачать pdf Руководство по установке и эксплуатации для Котел Advance Appliances ECB 210. Advance Appliances ECB 210 17 страниц. Electric combination boiler

PIPE WORK
In order to comply with Part L Building Regulations it is necessary to insulate
any hot water (primary and secondary) pipework within one metre of the
cylinder. Guidance is given in the Table 5 (Page 20) of the 2013 Domestic
Heating Compliance guide. Insulation values for the most popular pipe sizes
are reproduced below.
Pipe outside diameter

CENTRAL HEATING

The heating is connected to the lower 22mm tappings on the right hand
side of the tank. A pump is fitted with isolation valves. Fit the flow to
the heating to the pump connection.
Note that heating is vented and the water level in the header tank must
be 500mm above the highest radiator. Central heating is self
commissioning. Once it is connected the unit will fill automatically.
See page 11 on converting to a sealed system.
Radiators should be bled to remove any excess air from the system.
Use a two pipe system. Install thermostatic radiator valves but leave one
heat emitter fully open continually.
The system must be inhibited. Use a proprietary brand and recommended
dosage and concentration for central heating systems – don't forget the store
volume of 210 litres.
To prevent nuisance gravity circulation (in Summer for example when heating
is not required) a non return valve is fitted.
IMMERSION HEATERS
The highest position immersion heater is 3kW and should be wired to a
15amp switched spur. It can be used as a boost if extra demand is placed
on the hot water during the day.
The lower immersion heater is 6kW and is wired to come on (a)
when programmed to match off peak periods by programmer labelled
OFF PEAK and (b) to come on during heating periods when the wireless
room thermostat and programmer calls for heat. Instructions are supplied
with the programmers.
The 6kw immersion heater is controlled by the thermostat on the store.
15
22
28
35
Maximum heat loss in W/m
7
7.89
9.12
10.07
11.08