ETTO D2
INSTALLATION GUIDE
COPYRIGHT
Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written authorization,
except when regulated accordingly by the Copyright Laws.
WARRANTY
This product is covered by a warranty against material and manufacturing defects for a 24
months period from the manufacturing date.
The warranty does not cover the defects that are due to:
• Negligent and improper use
• Failures caused by atmospheric hazards
• Acts of vandalism
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products
The warranty is not applicable to the products that will result defective in consequence of a
negligent and improper use or an operating procedure not contemplated in this manual.
RETURN AND REPAIR FORMALITIES
Akse accepts the return of instruments for repair only when authorized in advance. The
transport costs are at customer charge.
RE-SHIPPING OF REPAIRED PRODUCT
The terms for re-shipment of repaired products are ex-works, i.e. the transport costs are
at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, will
be charged a fl at fee to account for checking and testing time irrespective of the warranty
terms.
SAFETY
This instrument was manufactured and tested in compliance with CEI EN 61010-1 CAT III-
300V, class 2 standards for operating voltages up to 300 VAC rms phase to neutral.
In order to maintain this condition and to ensure safe operation, the user must comply with
the indications and markings contained in the following instructions:
• When the instrument is received, before starting its installation, check that it is
intact and no damage occurred during transport.
• Before mounting, ensure that the instrument operating voltages and the mains
voltage are compatible then proceed with the installation.
• The instrument power supply needs no earth connection.
• The instrument is not equipped with a power supply fuse; a suitable external
!
protection fuse must be foreseen by the contractor.
• Maintenance and/or repair must be carried out only by qualifi ed, authorized
personnel
• If there is ever the suspicion that safe operation is no longer possible, the instrument
must be taken out of service and precautions taken againstits accidental use.
• Operation is no longer safe when:
1) There is clearly visible damage.
2) The instrument no longer functions.
3) After lengthy storage in unfavorable conditions.
4) After serious damage occurred during transport
The instruments must be installed in respect of all the local regulations.
OPERATOR SAFETY
Warning: Failure to observe the following instructions may lead to a serious danger of
death.
• During normal operation dangerous voltages can occur on instrument terminals.
Follow carefully the standard safety precautions while carrying out any installation or
service operation.
• The terminals of the instrument must not be accessible by the user after the installation.
The user should only be allowed to access the instrument front panel where the
display is located.
• The instrument must be protected by a breaking device capable of interrupting both
the power supply and the measurement terminals. It must be easily reachable by the
operator and well identifi ed as instrument cut-off device.
• The instrument and its connections must be carefully protected against short-circuit.
Precautions: Failure to respect the following instructions may irreversibly damage to the
instrument.
• The instrument is equipped with PTC current limiting device but a suitable external
protection fuse should be foreseen by the contractor.
• The outputs and the options operate at low voltage level; they cannot be powered by
any unspecifi ed external voltage.
• The application of currents not compatible with the current inputs levels will damage
to the instrument.
Further documentation may be downloaded from our web site www.electrex.it.
This document is owned by company AKSE that reserves all rights.
DECLARATION OF CONFORMITY
Akse hereby declares that its range of products complies with the following directives EMC
89/336/EEC
73/23CE
93/68 CE and complies with the following product's standard
CEI EN 61326 – IEC 61326
CEI EN 61010 – IEC 1010.
The product has been tested in the typical wiring confi guration and with peripherals
conforming to the EMC directive and the LV directive.
akse srl Via Aldo Moro, 39 42124 Reggio Emilia Italy
Tel. +39 0522 924 244 Fax +39 0522 924 245 [email protected] www.akse.it
P.I. 01544980350 R.E.A. 194296
Cap. Soc. Euro 85.800,00 i.v.
The meter is self-powered. Use cables with max cross-section of 2,5 mm2 if stranded or
4 mm2 if rigid and connect them to the instrument according to the applicable diagrams
that follow.
FUSE 32 AT
LOAD
1
2
3
Led
Counter
1600 imp/kWh
,
kWh
Etto
- +
5
4
100 imp/kWh
PULSE OUTPUT CONNECTION
WIRING EXAMPLE
1
2
3
Counter
Es. PLC
,
kWh
Etto
+
-
Vdc
Input
- +
5
4
100 imp/kWh
MECHANICAL CHARACTERISTICS
Case
Self-extinguish plastic class V0
Protection degree
IP40
Size
36 x 90 x 58 mm (2 DIN modules)
HARDWARE CHARACTERISTICS
Voltage Input
180 - 270 Vac
Current Input
Direct 5 (32) A
Impedance on input
1,5 MOhm
Precision
Class 1 on energy per IEC EN62053-21
Measure
R.M.S. up to 16th harmonics
Pulse output
Optoinsulated. 100 impulse / kWh according to regula-
tion DIN43864
Weight
100 g.
Temperature range
-10°C +50°C
Relative humidity
90% without condensation
Insulation
According VDE 0110 group C for exercise tension of 500
Vac rms
MODEL
PFAA280-C2
ETTO D2 230-240V ENERGY COUNTER
WIRING
PHASE
N
1
2
3
3 3
Tamper proof kit
Counter
,
kWh
Etto
- +
5
4
Tamper proof kit
Digital outputs (optocoupled NPN
transistor type for DiN 43864)
Maximum applicable voltage
27 Vdc
Maximum switchable current
27mA
1
2
3
230 Vac
Counter
Power
Supply
,
kWh
Max
Etto
27 Vdc
27 mA
- +
5
4
(-)
(+)
100 imp/kWh
- +
Subject to modifi cation without notice.
Edition 2015 04 24 MUL0068