Level measurement
®
LBFS
Point level detection
Operating Instructions
LBFS with the following process connections:
G 1/2 A ISO 228-1 BSC (BCID G07) with
„
„
industrial weld-in sleeve for universal use, Ø 30 x
26 (ZPW1-711, ZPW1-721)
G 1/2 A hygienic (BCID A03) with weld-in sleeve
„
„
or adapter from Baumer
For these process connections, do not seal with
Teflon tape (PTFE) or elastomer.
9 Vessel and pipelines are free of media.
9 Adapter or weld-in sleeve are mounted free of
dead space.
Screw in sensor.
f
„
Tightening torque: 15...20 Nm
LBFS with the following process connections:
G 1/2 A DIN 3852-E (BCID G51)
„
„
9 Vessel and pipelines are free of media.
Push the sealing ring on.
f
„
Screw in sensor.
f
„
Tightening torque: 15...20 Nm
LBFS with the following process connections:
G 1/2 A ISO 228-1 for internal installation (BCID
„
„
T10)
9 Vessel and pipelines are free of media.
Push the sealing ring on.
f
„
Screw in sensor.
f
„
Tightening torque: 15...20 Nm