Douglas Lighting Controls WRS-2224 Руководство по эксплуатации - Страница 8
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Сканер Douglas Lighting Controls WRS-2224. Douglas Lighting Controls WRS-2224 20 страниц. Programmable relay scanner
Setup: Input Configure Mode
INPUT CONFIGURE MODE
Allows specifying which type(s) of switching hardware can be
connected to each group switch input.
The default switch type for all inputs is the Douglas WR-8501
with Led Indicators. This configuration is compatible with all
models of Douglas relay switches, relay time clocks and photo
cells and no re-configuration is necessary for those devices.
However, if you will be connecting any different switch type(s)
to an input, follow this procedure.
To Use Input Configure Mode:
1. Make sure NORMAL MODE is selected. Its top indicator light should be ON.
2. Use the INPUT SELECT BUTTON to scroll to the group input #1-5 you
wish to configure (when its INPUT LED is ON).
3. Press and hold the OPTIONS MODE select button. The FLICK WARN LED
will begin flashing.
4. One of the OUTPUT LEDs #13-23 will display, showing the current
configuration selected for the input. Refer to the table below for a list of all
available configurations. The factory default is #21, the Douglas WR-
8501 LED indicator rectified AC pulse switch.
5. Depress the OUTPUT SELECT BUTTON(S) (#13-23) to select the desired
configuration(s) for the input.
You have 10 seconds to do this. After 10 seconds, the FLICK WARN LED
stops flashing and the scanner reverts to NORMAL mode.
6. Repeat steps 2-5 to configure other group inputs.
Output Button
Pressed
13
14
15
16
17
18
19
20
21 (Default)
22
23
WRS-2224: Directions & Applications
Switch Type Configured for
AC
Momentary
Contact.
AC
Maintained
Coil
Contact.
Rectified AC Pulse.
Current for Indicator LEDs.
LEDs
NOTE: Non-LED switches are also
compatible with this configuration.
Rectified AC Pulse.
No current for Indicator LEDs.
NOTE: LED switches will not function
properly with this configuration.
Table 1. Switch Hardware Type
page 6
Output Buttons
#13-#23
Flick
Warn
LED
Options Mode
Select Button
Action
(13)
ON when switched
-
(14)
OFF when switched
-
(15)
- OPEN=OFF / CLOSED=ON
(16)
- OPEN=ON / CLOSED=OFF
(17)
- OPEN=no action / CLOSED=ON
(18)
- OPEN=no action / CLOSED=OFF
(19)
- OPEN=ON / CLOSED=no action
(20)
- OPEN=OFF / CLOSED=no action
(21)
- Positive=OFF / Negative=ON
(22)
- Positive=ON / Negative=OFF
(23)
- Positive=OFF / Negative=ON
Output LEDs
#13-#23
Normal Mode
Select Button
Input
Select
Button
Input
LEDs
DOUGLAS