If you were programming a zone alarm LED you would select "Single Zone", then you would select the zone number
that will activate this LED (default zone 1). If we wanted to distinguish this LED if this were the first zone to alarm in
the system, you could check the box next to "Flash if Fire Started Here". As the default activation Qualifier is for an
alarm condition no further programming is required, when an alarm occurs in zone 1, the associated red LED will
illuminate.
If you wanted to also program a zone trouble LED, you would click on the yellow LED, the yellow LED would
illuminate and the LED Operation area will open up on the bottom left-hand side of the screen:
Within the LED Operation area, you would assign a Function Description for the LED and click on the "Unused"
description, within the Primary Activation Operating Method and a drop down menu will appear. You would then
select Single Zone:
After selecting "Single Zone", you would select the zone number that will activate this LED (default zone 1).
Note: All LEDs default to an Alarm qualifier, so if you want to program the LED to activate from a trouble
you need to remove (uncheck) the Alarm qualifier and add the trouble qualifier (check).