Advanced Axis AX-I/O-48 Руководство по установке
to perform. There are a number of Input Actions a switch or input can be assigned such as, create an alarm,
activate a control signal, disable a group of devices, disable a zone, acknowledge an event, reset the panel,
perform a drill, be an all call switch for audio, be a selective page switch, a lamp test a switch, etc.
Note: Based on the switch input action, programming of the switch type will be required, for example,
toggle (toggle on/off) or push button (one press activates requirements i.e. acknowledge, reset).
If you were programming a zone disable (bypass) switch, you would select the "Disable Zone" action. Once the
Disable Zone action has been selected you would input the zone number you'd like to disable within the
Disablement Zone number area (default is zone 1).

5.3 Buzzer Operation Programming

Each Switch LED Module has a programmable buzzer (piezo). The default programming of the buzzer is "Unused".
Like the LED programming of a switch LED module, the buzzer can be programmed for primary and secondary
activation.
Clicking on the buzzer of the module being programmed will open up a Buzzer Operation area on the bottom left-
hand side of the.
Within the Buzzer Operation area, you should assign a Function Description for the buzzer. After assigning a
Function Description, click on the "Unused" description within the Primary Activation Operating Method and a drop
down menu will appear allowing you to select the Operating Method of the buzzer; General Event, Single Zone,
Output Group or Disable Group control.
18