4 – Horizon Elite drain - specifier guidelines
Flush drain plumbing – For regular machine drainage
Minimum 8"
radius
2 ft x 1" OD
silicone tubing
3/4" barb x 3/4" FPT
3/4" MPT x 1" slip
1" Stand pipe/drain
Chassis drain plumbing – To assist with condensate in high humidity areas
5 – Horizon Elite ice tube runs - specifier guidelines
Long tube runs for RIDE remote ice delivery equipment
beverage
dispenser
minimum of
6.00" (15.24 cm)
turn/corner
ice transport tube –
1 3/16" OD,
2 1/8" OD with insulation
Remote 1010, 1410 series ice machine
support
maximum
straps
2' (60.9 cm)
radius
transport tube slope
(toward ice machine)
1/4"
1'
(2 cm per meter)
Important specifier notes: Where code allows,
follow recommendation below.
1. Connect the silicone tubing to the ice machine 3/4"
drain barb
2. Assemble the 3/4" barb x 3/4" FPT to the 3/4" MPT x 1"
slip. Connect the other end of the silicone tubing to the
3/4" barb
3. Connect the 1" slip fitting to the 1" stand pipe/drain
Note: Minimum 8" radius on silicone drain line. Drain line
from the ice machine must have at least 1/4" per foot
pitch (6.4 mm/0.3 m).
Note: Stand pipe/drain provided by others. All other
components provided with ice machine.
Important specifier notes: Where code allows,
follow recommendation below.
1. Plug must be removed from John Guest fitting.
2. Route 3/8" drain tubing through knockout in back of
docking station and insert fully into John Guest fitting
connection at the rear of the machine chassis. Route
other end of 3/8" drain tubing to drain.
3. Drain must slope 1/4" inch per foot ( 6 mm per 30.4 cm).
Important specifier notes
1. 75' (22.9 m) maximum ice transport tube run.
2. Tubing routing bends must have a
6.00" (15.24 cm) radius or larger.
3. Dips and traps are not allowed. If not
supported from underneath, secure insulated
ice transport tube at least every 2' (60.9 cm)
to prevent drips and traps.
4. Relative humidity levels above 80% in areas
where the ice machine or ice transport tube is
located may produce excessive condensation
that will cause water damage.
5. Contact factory for recommendations on
wall-mounted
running tubing through a decorative soffit
ice machine
or chase.
.
.
.