Advanced 56000-005ADV Инструкции по установке

Просмотреть онлайн или скачать pdf Инструкции по установке для Оборудование для обеспечения безопасности Advanced 56000-005ADV. Advanced 56000-005ADV 2 страницы. Dual action addressable manual polycarbonate pull station

Analog Value
AV=4:
Trouble
AV=16
Normal
AV=64:
Alarm State
Unit generates priority interrupt.
Output Bit
Function
2
LED
1 = On
0 = Off
1
TEST
1 = On
0 = Off
0
Not Used
Technical Data
Operating voltage
UL listed to operate
Current Consumption at 24V
Stand by current
LED Operated Alarm current
ADVANCED FIRE SYSTEMS INC.
100 South Street • Hopkinton, MA 01748
Telephone: (508) 453-9995
APD0519 A130107
Input Bit
Function
2
LED Confirmed
1 = On
0 = Off
1
1 in normal state
0 in alarm state
0
0 in normal state
1 in alarm state
17-28V DC
20-28V DC
200µA
3.6mA + Quiescent
www.afsi.us.com
4
56000-005ADV
Dual Action Addressable
Manual Polycarbonate Pull Station
Installation Instructions
The Dual Action Polycarbonate Addressable Manual Pull Station may be flush
mounted on a single gang electrical box, or it may be surface mounted using the
Pull Station Polycarbonate Back Box (56000-006, sold separately). Be sure to follow
local codes and regulations. To comply with ADA standards, the Pull Station must be
connected less than 48 inches above floor level for front wheelchair access, and less
than 54 inches for side wheel chair access.
Control Panel Compatibility
Compatibility Identifier number: 56000-005ADV. The module has been approved
by Underwriters Laboratories Inc. The pull station is compatible with Advanced Fire
Systems Inc's AX Series fire control panels. Contact Advanced Fire Systems Inc or refer
to the Fire Alarm Control Unit's installation manual for more details.
Set the address using the DIP switches in accordance with the address table overleaf.
Open the Pull Station using the included key, turning the key to the right and allowing
the Pull Station to open out.
With the Pull Station open, carefully undo the clear protective cover to the circuit
board area. The cover should open out, hinging from the bottom, closest to the
alarm switch. If the clear protective cover comes off completely, replace the cover
by making sure that the protruding pivot points are positioned down, toward the
alarm switch, and aligned with the corresponding slots.
Program the address of the station using the DIP switches under the clear protective
cover. When address programming is completed, apply equal pressure over the
upper tabs of the cover until it snaps into place and is secure.
See Fig 1 for wiring options.
If using the Pull Station Polycarbonate Back Box (56000-006), attach to the wall
using four #8 screws that are appropriate for the wall type or anchor. Verify that the
orientation of the box is as shown in Figure 1 on the following page, with the arrows
inside the box pointing UP. Connect the ½ NPT conduit to the top or bottom of the
box and run the wiring as required by the application. Make sure that the wires at the
back of the pull station are not pinched by the electrical box during installation.
Close and lock the station using the key provided. Test the station as required by the
local code and the particular installation.
Reset the station by opening and closing it.
1