(1) Install insulation for the drain pipe.
Assemble as described below.
Assemble Drain hose (Accessories) and Hose band
(Accessories) to Drain port.
Soft PVC side
10 to 15 mm
Drain hose
(Accessories)
Wrap the drain hose insulation around the drain hose connection.
Drain hose insulation
(Accessories)
Hose opening view
Wind the attached heat insulation around the
hose band. Make sure the alignment is on top.
100mm
En-7
Drain port
Hose band
Drain hose
(Accessories)
(Accessories)
Drain pan
Ensure there is no space
Hose band
(Accessories)
Soft PVC side
(2) If " ① Right rear piping": fasten the drain hose with VT wire so that the pipe slopes
correctly within the indoor unit.
Indoor unit (Rear view)
(3) Connect the drain pipe.
Hard PVC side
6. ELECTRICAL WIRING
Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
Use the included connection cables and power cables or ones specified by the manu-
facturer. Improper connections, insufficient insulation, or exceeding the allowable current
can cause electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections. Improp-
erly connected or secured cables can cause serious accidents such as overheating the
terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal board numbers and connection cable colors with those of the out-
door unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical box
cover can cause serious accidents such as electric shock or fire through exposure to
dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Install an earth leakage breaker. In addition, install the earth leakage breaker so that the
entire AC main power supply is cut off at the same time. Otherwise, electric shock or fire
could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may
cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
VT wire (Accessories)
Drain hose
Applying
area of
Joint pipe
adhesive
(locally purchased)
Drain pipe (VP25)
(locally purchased)
4 mm or less
WARNING