Drain Master DM-150 Инструкция по эксплуатации - Страница 7

Просмотреть онлайн или скачать pdf Инструкция по эксплуатации для Водяной насос Drain Master DM-150. Drain Master DM-150 12 страниц. Condensate auto drain

ELECTRICAL INSTALLATION
ELECTRICAL DATA
12 PAGE
Power Voltage
Max, Power input
Recommanded cable jacket diameter
Cable cross-section and fuse protection
Contact loading relay or out
▶ The emergency relay will be activated when there is no operation pressure (0.8 bar) or with an error signal,
switching the system to the alarm mode
12
0.0
Phase
0.1
Neutral
0.2
Ground
0.3
0.4
24 VDC
0.5
0.6
Normally closed
0.7
Common
0.8
Normally open
90 ~ 240/ 24/ 48 Vac
24 / 48 Vdc
P < 2.0 VA
P < 2.0 W
Ø 5.8 ~ 8.0 mm
3 x 0.75 mm
2
/ 5 x 0.25 mm
2
0.5 A
100 mA
260 Vac - < 1.0 A
Trouble shooting
▶ No discharge of condensate
with the Test button
▶ Condensate only discharged
when the Test button is pressed
Power
and held
Valve
▶ Power lamp not lit
Alarm
▶ Continuous air discharge from
the valve
MAINTENANCE
Factor
※ The feed line or the discharge
Check these lines.
line is closed or blocked.
※ Defective PCB
Replace the PCB.
※ Defective solenoid valve
Replace the solenoid valve.
Replace the worn parts
※ Worn parts
(Wearing part kits)
※ Pressure is lower than 0.8 bar
Check the operation pressure.
※ Insufficient pipe slope with
Add slop to the feed line, or install
the feed line
a vent line.
※ The pipe length for feed line
Install an air vent line
is too long
(see Installation Method)
※ Overload due to excessive
Select a correct model for the
condensate
volume of condensate.
※ Detection disabled by excessive
Clean the sensor tube.
contamination on the sensor tube
Check the rated voltage.
※ Power not connected.
Check the cable connection.
※ Defective PCB
Replace the PCB
※ The lower part of the diaphragm
is contaminated by foreign materials
Remove foreign materials.
(scale etc)
※ The 'control air line' is blocked.
Remove foreign materials.
※ Poor operation due to foreign
Clean the valve.
materials inside the solenoid valve
※ Worn parts.
Replace the worn parts.
(Diaphragm. Plunger etc)
▶Clean the housing and valves 1-2 times a year.
▶Check wearing parts once a year.
▶Wearing parts
DM-5S
SP DM5S 101
DM-5
SP DM5 101
DM-5N
SP DM5N 101
DM-15
SP DM15 101
DM-50
SP DM50 101
DM-150
SP DM150 101
DM-500
SP DM500 101
DM-1500
SP DM1500 101
DM-15HP
SP DM15H 101
DM-50HP
SP DM50H 101
DM-150HP
SP DM150H 101
Solution
13