AirStage ASHE007GTAH Руководство по установке - Страница 10
Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер AirStage ASHE007GTAH. AirStage ASHE007GTAH 15 страниц. Indoor unit (floor type)
Также для AirStage ASHE007GTAH: Руководство по эксплуатации (8 страниц)
6.3. Function setting
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "6.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
Filter
indicator
11
01 Longer
interval
02 Shorter
00 Enable
01 Disable
Filter
indicator
13
Display only
action
on central
02
remote
controller
(Forbidden)
23
00
00 Standard
Horizontal
swing
24
01 Left half
airflow
direction
02 Right half
00 Standard
Cool air
tempera-
30
01 Adjust (1)
ture trigger
02 Adjust (2)
00 Standard
Heat air
01 Adjust (1)
tempera-
31
02 Adjust (2)
ture trigger
03 Adjust (3)
00 Enable
Auto restart
40
01 Disable
00 Super low
Cool Air
Follow the
43
Prevention
setting on
01
the remote
controller
00 Start/Stop
External
46
Emergency
control
01
stop
02 Forced Stop
En-9
WARNING
Default
Details
○
Adjust the filter cleaning interval
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
○
Enable or disable the filter indica-
tor. Setting 02 is for use with a
central remote controller.
○
○
Adjust the horizontal swing airflow
direction.
(For horizontal swing equipped
models)
○
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
○
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor
○
unit by this function in normal
operation.
Be sure to operate by the control
unit, converter or external input
device.
○
Restrain the cold airflow with mak-
ing the airflow lower when starting
heating operation. To correspond to
○
the ventilation, set to 01.
Allow an external controller to start
○
or stop the system, or to perform
an emergency stop.
If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
00 All
Display only
Error report
47
target
on central
01
remote
controller
Follow the
Fan setting
setting on
when
00
the remote
cooling
49
controller
thermostat
OFF
01 Stop
(Forbidden)
60
00
(Forbidden)
61
00
(Forbidden)
62
00
Single set-
point auto
00
mode
Auto mode
(traditional)
68
type
Dual set-
point auto
01
mode
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
04 2.0°C
Deadband
69
value
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
6.3.1 Indoor unit indicator lamps
004/007/009 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
030/034 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
○
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the
central remote controller.
When set to 01, the fan stops when
○
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
○
○
○
Switch the setting method of
○
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master indoor
unit (by wired remote controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).